﻿//L300P

[CMD-SigData]
00_00        Command – 00    0: Stop command, 1:Forward command, 2:Reverse command
01_00        Command – 01    Output frequency setting for the standard profile 
02_00        Command – 02    Low 32-bit data setting of intelligent terminal state
02_00.00   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [FW] Forward command
02_00.01   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [RV] Reverse command
02_00.02   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [CF1] Multi-speed 1
02_00.03   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [CF2] Multi-speed 2
02_00.04   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [CF3] Multi-speed 3
02_00.05   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [CF4] Multi-speed 4
02_00.06   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [JG] Jog operation
02_00.07   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [DB] Dynamic braking
02_00.08   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [SET] set 2nd motor
02_00.09   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [2CH] 2-stage adjustable speed
02_00.11   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [FRS] Free-run stop
02_00.12   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [EXP] External trip
02_00.13   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [USP] Unattended start protection
02_00.14   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [CS] Commercial power change
02_00.15   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [SFT] Software lock
02_00.16   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [AT] analog input voltage/current
02_00.18   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [RS] Reset
02_00.20   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [STA] 3-wire Start
02_00.21   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [ST]P 3-wire Hold
02_00.22   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [F/R] 3-wire FWD/REV
02_00.23   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [PID] PID enable
02_00.24   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [PIDC] PID integrator reset
02_00.27   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [UP] remote control increment speed
02_00.28   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [DWN] remote control decrement speed
02_00.29   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [UDC] remote control clear up/down
02_00.31   Command – 02    Lower 32 bits of 64-bit Intelligent Terminal Status data: [OPE] Force from operator terminal
02_01        Command – 02    High 32-bit data setting of intelligent terminal state
02_01.00   Command – 02    Higher 32 bits of 64-bit Intelligent Terminal Status data: [SF1] Multi-speed bit-level
02_01.01   Command – 02    Higher 32 bits of 64-bit Intelligent Terminal Status data: [SF2] Multi-speed bit-level
02_01.02   Command – 02    Higher 32 bits of 64-bit Intelligent Terminal Status data: [SF3] Multi-speed bit-level
02_01.03   Command – 02    Higher 32 bits of 64-bit Intelligent Terminal Status data: [SF4] Multi-speed bit-level
02_01.04   Command – 02    Higher 32 bits of 64-bit Intelligent Terminal Status data: [SF5] Multi-speed bit-level
02_01.05   Command – 02    Higher 32 bits of 64-bit Intelligent Terminal Status data: [SF6] Multi-speed bit-level
02_01.06   Command – 02    Higher 32 bits of 64-bit Intelligent Terminal Status data: [SF7] Multi-speed bit-level
02_01.07   Command – 02    Higher 32 bits of 64-bit Intelligent Terminal Status data: [OLR] Overload restriction setting
03_00        Command – 03    Output frequency 
03_01        Command – 03    Output current 
03_02        Command – 03    Direction of rotation 
03_03        Command – 03    PID feedback monitor 
03_04        Command – 03    Intelligent input monitor 
03_04.00   Command – 03    Intelligent input monitor: Forward input
03_04.01   Command – 03    Intelligent input monitor: Input 1
03_04.02   Command – 03    Intelligent input monitor: Input 2
03_04.03   Command – 03    Intelligent input monitor: Input 3
03_04.04   Command – 03    Intelligent input monitor: Input 4
03_04.05   Command – 03    Intelligent input monitor: Input 5
03_04.06   Command – 03    Intelligent input monitor: Input 6
03_04.07   Command – 03    Intelligent input monitor: Input 7
03_04.08   Command – 03    Intelligent input monitor: Input 8
03_05        Command – 03    Intelligent output monitor 
03_05.00   Command – 03    Intelligent output monitor: Alarm relay
03_05.01   Command – 03    Intelligent output monitor: Output 1
03_05.02   Command – 03    Intelligent output monitor: Output 2
03_05.03   Command – 03    Intelligent output monitor: Output 3
03_05.04   Command – 03    Intelligent output monitor: Output 4
03_05.05   Command – 03    Intelligent output monitor: Output 5
03_06        Command – 03    Frequency converting monitor 
03_08        Command – 03    Output voltage monitor
03_09        Command – 03    Electric power monitor
03_11        Command – 03    Run Mode time monitor 
03_12        Command – 03    Power ON time monitor 
04_00        Command – 04    Status A 
04_01        Command – 04    Status B 
04_02        Command – 04    Status C 
05_00        Command – 05    Total count
05_01        Command – 05    [Trip 1]  Trip factor
05_02        Command – 05    [Trip 1]  Inverter Status A
05_03        Command – 05    [Trip 1]  Inverter Status B
05_04        Command – 05    [Trip 1]  Inverter Status C
05_05        Command – 05    [Trip 1]  Output frequency
05_06        Command – 05    [Trip 1]  Accumulated Run Mode time
05_07        Command – 05    [Trip 1]  Output current
05_08        Command – 05    [Trip 1]  Output voltage
05_09        Command – 05    [Trip 1]  Power ON timer
05_10        Command – 05    [Trip 2]  Trip factor
05_11        Command – 05    [Trip 2]  Inverter Status A
05_12        Command – 05    [Trip 2]  Inverter Status B
05_13        Command – 05    [Trip 2]  Inverter Status C
05_14        Command – 05    [Trip 2]  Output frequency
05_15        Command – 05    [Trip 2]  Accumulated Run Mode time
05_16        Command – 05    [Trip 2]  Output current
05_17        Command – 05    [Trip 2]  Output voltage
05_18        Command – 05    [Trip 2]  Power ON timer
05_19        Command – 05    [Trip 3]  Trip factor
05_20        Command – 05    [Trip 3]  Inverter Status A
05_21        Command – 05    [Trip 3]  Inverter Status B
05_22        Command – 05    [Trip 3]  Inverter Status C
05_23        Command – 05    [Trip 3]  Output frequency
05_24        Command – 05    [Trip 3]  Accumulated Run Mode time
05_25        Command – 05    [Trip 3]  Output current
05_26        Command – 05    [Trip 3]  Output voltage
05_27        Command – 05    [Trip 3]  Power ON timer
05_28        Command – 05    [Trip 4]  Trip factor
05_29        Command – 05    [Trip 4]  Inverter Status A
05_30        Command – 05    [Trip 4]  Inverter Status B
05_31        Command – 05    [Trip 4]  Inverter Status C
05_32        Command – 05    [Trip 4]  Output frequency
05_33        Command – 05    [Trip 4]  Accumulated Run Mode time
05_34        Command – 05    [Trip 4]  Output current
05_35        Command – 05    [Trip 4]  Output voltage
05_36        Command – 05    [Trip 4]  Power ON timer
05_37        Command – 05    [Trip 5]  Trip factor
05_38        Command – 05    [Trip 5]  Inverter Status A
05_39        Command – 05    [Trip 5]  Inverter Status B
05_40        Command – 05    [Trip 5]  Inverter Status C
05_41        Command – 05    [Trip 5]  Output frequency
05_42        Command – 05    [Trip 5]  Accumulated Run Mode time
05_43        Command – 05    [Trip 5]  Output current
05_44        Command – 05    [Trip 5]  Output voltage
05_45        Command – 05    [Trip 5]  Power ON timer
05_46        Command – 05    [Trip 6]  Trip factor
05_47        Command – 05    [Trip 6]  Inverter Status A
05_48        Command – 05    [Trip 6]  Inverter Status B
05_49        Command – 05    [Trip 6]  Inverter Status C
05_50        Command – 05    [Trip 6]  Output frequency
05_51        Command – 05    [Trip 6]  Accumulated Run Mode time
05_52        Command – 05    [Trip 6]  Output current
05_53        Command – 05    [Trip 6]  Output voltage
05_54        Command – 05    [Trip 6]  Power ON timer
08_00        Command – 08    Initializes the inverter parameters to the factory default values
09_00        Command – 09    Check whether Setting Values can be saved to EEPROM or not
0A_00        Command – 0A    Save Setting Values to EEPROM
0B_00        Command – 0B    Recalculates internal motor constants
0E_00        Command – 0E    Read Output Frequency Setting Value
[CMD-SigDataEnd]

[F-SigData]
F002	Acceleration (1) time setting
F202	Acceleration (1) time setting, 2nd motor
F003	Deceleration (1) time setting
F203	Deceleration (1) time setting, 2nd motor
F004	Keypad Run key routing
[F-SigDataEnd]

[A-SigData]
A001	Frequency source setting
A002	Run command source setting
A003	Base frequency setting
A203	Base frequency setting, 2nd motorr
A004	Maximum frequency setting
A204	Maximum frequency setting, 2nd motor
A005	[AT] selection
A006	[O2] selection
A011	[O]-[L] input active range start frequency
A012	[O]-[L] input active range end frequency
A013	[O]-[L] input active range start voltage
A014	[O]-[L] input active range end voltage
A015	[O]-[L] input start frequency enable
A016	External frequency filter time constant
A019	Multi-speed operation selection
A020	Multi-speed frequency setting
A220	Multi-speed frequency setting, 2nd motor
A021	Multi-speed 1 setting
A022	Multi-speed 2 setting
A023	Multi-speed 3 setting
A024	Multi-speed 4 setting
A025	Multi-speed 5 setting
A026	Multi-speed 6 setting
A027	Multi-speed 7 setting
A028	Multi-speed 8 setting
A029	Multi-speed 9 setting
A030	Multi-speed 10 setting
A031	Multi-speed 11 setting
A032	Multi-speed 12 setting
A033	Multi-speed 13 setting
A034	Multi-speed 14 setting
A035	Multi-speed 15 setting
A038	Jog frequency setting
A039	Jog stop mode
A041	Torque boost method selection
A241	Torque boost method selection, 2nd motor
A042	Manual torque boost value
A242	Manual torque boost value, 2nd motor
A043	Manual torque boost frequency adjustment
A243	Manual torque boost frequency adjustment, 2nd motor
A044	V/F characteristic curve selection, 1st motor
A244	V/F characteristic curve selection, 2nd motor
A045	V/F gain setting
A051	DC braking enable
A052	DC braking frequency setting
A053	DC braking wait time
A054	DC braking force during deceleration
A055	DC braking time for deceleration
A056	DC braking / edge or level detection for [DB] input
A057	DC braking force for starting
A058	DC braking time for starting
A059	DC braking carrier frequency setting
A061	Frequency upper limit setting
A261	Frequency upper limit setting, 2nd motor
A062	Frequency lower limit setting
A262	Frequency lower limit setting, 2nd motor
A063	Jump (center) frequency setting
A064	Jump (hysteresis) frequency width setting
A065	Jump (center) frequency setting
A066	Jump (hysteresis) frequency width setting
A067	Jump (center) frequency setting
A068	Jump (hysteresis) frequency width setting
A069	Acceleration pause frequency setting     
A070	Acceleration pause time setting          
A071	PID Function Enable
A072	PID proportional gain
A073	PID integral time constant
A074	PID derivative time constant
A075	PV scale conversion
A076	PV source setting
A081	AVR function select
A082	AVR voltage select
A085	Operation mode selection
A086	Energy saving mode tuning
A092	Acceleration (2) time setting
A292	Acceleration (2) time setting, 2nd motor
A093	Deceleration (2) time setting
A293	Deceleration (2) time setting, 2nd motor
A094	Select method to switch to Acc2/Dec2 profile
A294	Select method to switch to Acc2/Dec2 profile, 2nd motor
A095	Acc1 to Acc2 frequency transition point
A295	Acc1 to Acc2 frequency transition point, 2nd motor
A096	Dec1 to Dec2 frequency transition point 
A296	Dec1 to Dec2 frequency transition point, 2nd motor 
A097	Acceleration curve selection
A098	Deceleration curve selection
A101	[OI]–[L] input active range start frequency
A102	[OI]-[L] input active range end frequency
A103	[OI]–[L] input active range start current
A104	[OI]–[L] input active range end current  
A105	[OI]-[L] input start frequency enable
A111	[O2]-[L] input active range start frequency
A112	[O2]-[L] input active range end frequency
A113	[O2]-[L] input active range start voltage
A114	[O2]-[L] input active range end voltage
A131	Acceleration curve constants setting
A132	Deceleration curve constants setting
[A-SigDataEnd]

[b-SigData]
b001	Selection of automaticrestart mode
b002	Allowable under-voltage power failure time
b003	Retry wait time before motor restart
b004	Instantaneous power failure / under-voltage trip alarm enable
b005	Number of restart on power failure / under-voltage trip events
b006	Phase loss detection enable
b007	Restart frequency threshold
b012	Level of electronic thermal setting           
b212	Level of electronic thermal setting, 2nd motor
b013	Electronic thermal characteristic
b213	Electronic thermal characteristic, 2nd motor
b015	Free setting, electronic thermal frequency (1)
b016	Free setting, electronic thermal current (1)
b017	Free setting, electronic thermal frequency (2)
b018	Free setting, electronic thermal current (2)
b019	Free setting, electronic thermal frequency (3)
b020	Free setting, electronic thermal current (3)
b021	Overload restriction operation mode
b022	Overload restriction setting
b023	Deceleration rate at overload restriction
b024	Overload restriction operation mode (2)
b025	Overload restriction setting (2)
b026	Deceleration rate at overload restriction (2)
b031	Software lock mode selection
b034	Run/power-on warning time
b035	Rotational direction restriction
b036	Reduced voltage start selection
b037	Function code display restriction
b080	[AM] terminal analog meter adjustment
b081	[FM] terminal analog meter adjustment
b082	Start frequency adjustment
b083	Carrier frequency setting
b084	Initialization mode (parameters or trip history)
b085	Country code for initialization
b086	Frequency scaling conversion factor
b087	STOP key enable
b088	Restart mode after FRS
b090	Dynamic braking usage ratio
b091	Stop mode selection
b092	Cooling fan control
b095	Dynamic braking control
b096	Dynamic braking activation level
b098	Thermistor for thermal protection control
b099	Thermal protection level setting
b100	Free-setting V/f frequency (1)
b101	Free-setting V/f voltage (1)
b102	Free-setting V/f frequency (2)
b103	Free-setting V/f voltage (2)
b104	Free-setting V/f frequency (3)
b105	Free-setting V/f voltage (3)
b106	Free-setting V/f frequency (4)
b107	Free-setting V/f voltage (4)
b108	Free-setting V/f frequency (5)
b109	Free-setting V/f voltage (5)
b110	Free-setting V/f frequency (6)
b111	Free-setting V/f voltage (6)
b112	Free-setting V/f frequency (7)
b113	Free-setting V/f voltage (7)
[b-SigDataEnd]

[C-SigData]
C001	Terminal [1] function
C002	Terminal [2] function
C003	Terminal [3] function
C004	Terminal [4] function
C005	Terminal [5] function
C011	Terminal [1] active state
C012	Terminal [2] active state
C013	Terminal [3] active state
C014	Terminal [4] active state
C015	Terminal [5] active state
C019	Terminal [FW] active state
C021	Terminal [11] function
C022	Terminal [12] function
C026	Alarm relay terminal function
C027	[FM] signal selection
C028	[AM] signal selection
C029	[AMI] signal selection
C031	Terminal [11] active state
C032	Terminal [12] active state
C036	Alarm relay terminal active state
C040	Overload signal output mode
C041	Overload level setting
C042	Frequency arrival setting for acceleration
C043	Arrival frequency setting for deceleration
C044	PID deviation level setting
C061	Electronic thermal warning level setting
C070	Data command method
C071	Communication speed selection 
C072	Node allocation
C073	Communication data length selection
C074	Communication parity selection
C075	Communication stop bit selection
C078	Communication wait time
C081	[O] input span calibration
C082	[O1] input span calibration
C083	[O2] input span calibration
C085	Thermistor input tuning
C086	[AM] terminal offset tuning
C087	[AMI] terminal meter tuning
C088	[AMI] terminal offset tuning
C091	Debug mode enable
C101	Up/Down memory mode selection
C102	Reset mode selection
C103	Restart mode after reset
C121	[O] input zero calibration
C122	[O1] input zero calibration
C123	[O2] input zero calibration
[C-SigDataEnd]

[H-SigData]
H003	Motor capacity, 1st motor
H203	Motor capacity, 2nd motor
H004	Motor poles setting, 1st motor
H204	Motor poles setting, 2nd motor 
H006	Motor stabilization constant, 1st motor
H206	Motor stabilization constant, 2nd motor
[H-SigDataEnd]

[P-SigData]
P001	Operation mode on expansion card 1 error
P002	Operation mode on expansion card 2 error
P031	Accel/decel time input selection
P044	DeviceNet comm watchdog timer
P045	Inverter action on DeviceNet comm error
P046	DeviceNet polled I/O: Output instance number
P047	DeviceNet polled I/O: Input instance number
P048	Inverter action on DeviceNet idle mode
P049	Motor poles setting for RPM
[P-SigDataEnd]