﻿Series:X200
DataFormat=Hex

[SigData]
00001	Run command
00002	FW/RV command
00003	External trip (EXT)
00004	Trip reset (RS)
00007	Intelligent input terminal 1
00008	Intelligent input terminal 2
00009	Intelligent input terminal 3
0000A	Intelligent input terminal 4
0000B	Intelligent input terminal 5
0000E	Run/Stop status
0000F	FW/RV status
00010	Inverter ready
00014	Alarm signal
00015	PID deviation signal
00016	Overload signal
00017	Frequency arrival signal(set frequency or above)
00018	Frequency arrival signal(at constant speed)
00019	Run Mode signal
0001A	Data writing
0001B	CRC error
0001C	Overrun error
0001D	Framing error
0001E	Parity error
0001F	Check sum error
40002	Output frequency command
40003	Inverter status
40005	Process Variable (PV)
40011	Trip counter
40012	Trip monitor 1: factor code
40014	Trip monitor 1: Frequency
40016	Trip monitor 1: Current
40017	Trip monitor 1: Voltage
40018	Trip monitor 1: Run time (high)
40019	Trip monitor 1: Run time (low)
4001A	Trip monitor 1: ON time (high)
4001B	Trip monitor 1: ON time (low)
4001C	Trip monitor 2: factor code
4001E	Trip monitor 2: Frequency
40020	Trip monitor 2: Current
40021	Trip monitor 2: Voltage
40022	Trip monitor 2: Run time (high)
40023	Trip monitor 2: Run time (low)
40024	Trip monitor 2: ON time (high)
40025	Trip monitor 2: ON time (low)
40026	Trip monitor 3: factor code
40028	Trip monitor 3: Frequency
4002A	Trip monitor 3: Current
4002B	Trip monitor 3: Voltage
4002C	Trip monitor 3: Run time (high)
4002D	Trip monitor 3: Run time (low)
4002E	Trip monitor 3: ON time (high)
4002F	Trip monitor 3: ON time (low)
40900	ENTER Command
41002	Output frequency monitor
41003	Output current monitor
41004	Rotation direction monitor
41005	Process Variable (PV), PID feedback monitor (high)
41006	Process Variable (PV), PID feedback monitor (low)
41007	Intelligent input terminal status
41008	Intelligent output terminal status
41009	Scaled output frequency monitor (high)
4100A	Scaled output frequency monitor (low)
4100C	Output voltage monitor
4100E	Cumulative operation RUN time monitor (high)
4100F	Cumulative operation RUN time monitor (low)
41010	Cumulative power-on time monitor (high)
41011	Cumulative power-on time monitor (low)
41014	Acceleration (1) time setting (high)
41015	Acceleration (1) time setting (low)
41016	Deceleration (1) time setting (high)
41017	Deceleration (1) time setting (low)
41018	Keypad Run key routing
41019	Frequency source setting
4101A	Run command source setting
4101B	Base frequency setting
4101C	Maximum frequency setting
4101D	[AT] selection
41020	O–L input active range start frequency
41022	O–L input active range end frequency
41023	O–L input active range start voltage
41024	O–L input active range end voltage
41025	O–L input start frequency enable
41026	External frequency filter time constant
41029	Multi-speed 0 setting
4102B	Multi-speed 1 setting
4102D	Multi-speed 2 setting
4102F	Multi-speed 3 setting
41031	Multi-speed 4 setting
41033	Multi-speed 5 setting
41035	Multi-speed 6 setting
41037	Multi-speed 7 setting
41039	Multi-speed 8 setting
4103B	Multi-speed 9 setting
4103D	Multi-speed 10 setting
4103F	Multi-speed 11 setting
41041	Multi-speed 12 setting
41043	Multi-speed 13 setting
41045	Multi-speed 14 setting
41047	Multi-speed 15 setting
41048	Jog frequency setting
41049	Jog stop mode
4104A	Torque boost select
4104B	Manual torque boost value
4104C	Manual torque boost frequency adjustment
4104D	V/f characteristic curve selection
4104E	V/f gain setting
41051	DC braking enable
41052	DC braking frequency setting
41053	DC braking wait time
41054	DC braking force for deceleration
41055	DC braking time for deceleration
41056	DC braking / edge or level detection for [DB] input
4105A	Frequency upper limit setting
4105B	Frequency lower limit setting
4105D	Jump (center) frequency setting
4105E	Jump (hysteresis) frequency width setting
41060	Jump (center) frequency setting
41061	Jump (hysteresis) frequency width setting
41063	Jump (center) frequency setting
41064	Jump (hysteresis) frequency width setting
41068	PID enable
41069	PID proportional gain
4106A	PID integral time constant
4106B	PID derivative time constant
4106C	PV scale conversion
4106D	PV source setting
4106E	Reverse PID action
4106F	PID output limit
41070	AVR function select
41071	AVR voltage select
41072	Operation mode selection
41073	Energy saving mode tuning
41074	Acceleration (2) time setting (high)
41075	Acceleration (2) time setting (low)
41076	Deceleration (2) time setting (high)
41077	Deceleration (2) time setting (low)
41078	Select method to switch to Acc2/Dec2 profile
4107A	Acc1 to Acc2 frequency transition point
4107C	Dec1 to Dec2 frequency transition point
4107D	Acceleration curve selection
4107E	Deceleration curve selection
41080	[OI]-[L] input active range start frequency
41082	[OI]-[L] input active range end frequency
41083	[OI]-[L] input active range start current
41084	[OI]-[L] input active range end voltage
41085	[OI]-[L] input start frequency enable
4108E	A input select for calculate function
4108F	B input select for calculate function
41090	Calculation symbol
41091	ADD frequency
41093	ADD direction select
41095	POT active range start frequency
41097	POT input active range end frequency
41098	POT input active range start
41099	POT input active range end
4109A	POT input start frequency enable
410A5	Selection of automatic restart mode
410A6	Allowable under-voltage power failure time
410A7	Retry wait time before motor restart
410A8	Instantaneous power failure / under-voltage trip alarm enable
410A9	Number of restarts on power failure / under-voltage trip events
410AD	Level of electronic thermal setting
410AE	Electronic thermal characteristic
410B5	Overload restriction operation mode
410B6	Overload restriction level setting
410B7	Deceleration rate at overload restriction
410BB	Source of overload restriction selection
410BC	Software lock mode selection
410C9	Selection of the non stop operation
410CA	Non stop operation start voltage setting
410CB	OV-LAD Stop level of non stop operation setting
410CC	Deceleration time of non stop operation setting
410CE	Frequency width of quick deceleration setting
410CF	[AM]analog signal gain
410D1	Start frequency adjustment
410D2	Carrier frequency setting
410D3	Initialization mode (parameters or trip history)
410D4	Country for initialization
410D5	Frequency scaling conversion factor
410D6	STOP key enable
410D7	Restart mode after FRS
410D8	Monitor display select for networked inverter
410DA	Stop mode selection
410DB	Cooling fan control
410F5	Over-voltage LADSTOP enable
410F6	Over-voltage LADSTOP level
410F7	Over-current trip suppression
410F8	Carrier mode
410F9	Selection of RDY function
41103	Terminal [1] function
41104	Terminal [2] function
41105	Terminal [3] function
41106	Terminal [4] function
41107	Terminal [5] function
4110B	Terminal [1] active state
4110C	Terminal [2] active state
4110D	Terminal [3] active state
4110E	Terminal [4] active state
4110F	Terminal [5] active state
41114	Terminal [11] function
41119	Alarm relay terminal function
4111B	[AM] signal selection
4111D	Terminal [11] active state
41122	Alarm relay active state
41124	Overload level setting
41126	Frequency arrival setting for acceleration
41128	Frequency arrival setting for deceleration
41129	PID deviation level setting
4112E	PID FBV function high limit
4112F	PID FBV function variable low limit
41137	Selection of OPE / ModBus
41138	Communication speed selection
41139	Node allocation
4113B	Communication parity selection
4113C	Communication stop bit selection
4113D	Communication error select
4113E	Communication error time-out
4113F	Communication wait time
41141	O input span calibration
41142	OI input span calibration
41145	AM offset calibration
41149	Up/Down memory mode selection
4114A	Reset selection
41150	Input A select for logic output
41151	Input B select for logic output
41152	Logic function select
41153	Terminal [11] ON delay
41154	Terminal [11] OFF delay
41157	Output relay ON delay
41158	Output relay OFF delay
41165	Motor capacity
41166	Motor poles setting
41168	Motor stabilization constant
4116A	Fin temperature monitor
4116C	DC voltage monitor
4116D	Electronic thermal monitor
41170	Start freq to be used in case of freq pull-in restart
41171	Deceleration rate of frequency pull-in restart setting
41172	Current level of frequency pull-in restart setting
41173	DC bus AVR P-gain
41174	DC bus AVR I-time
41176	DC bus AVR selection
41177	Threshold voltage of DC bus AVR setting
41178	Output mode of low load detection signal
41179	Low load detection level
41501	Acceleration (1) time setting, 2nd motor (high)
41502	Acceleration (1) time setting, 2nd motor (low)
41503	Deceleration (1) time setting, 2nd motor (high)
41504	Deceleration (1) time setting, 2nd motor (low)
4150C	Base frequency setting, 2nd motor
4150D	Maximum frequency setting, 2nd motor
4150F	Multi-speed 0 setting 2nd motor
41510	Torque boost select, 2nd motor
41511	Manual torque boost value, 2nd motor
41512	Manual torque boost frequency adjustment, 2nd motor
41513	V/f characteristic curve selection, 2nd motor
41514	V/f gain setting, 2nd motor
41517	Frequency upper limit setting, 2nd motor
41518	Frequency lower limit setting, 2nd motor
41519	Acceleration (2) time setting, 2nd motor (high)
4151A	Acceleration (2) time setting, 2nd motor (low)
4151B	Deceleration (2) time setting, 2nd motor (high)
4151C	Deceleration (2) time setting, 2nd motor (low)
4151D	Select method to switch to Acc2/Dec2 profile, 2nd motor
4151F	Acc1 to Acc2 frequency transition point, 2nd motor
41521	Dec1 to Dec2 frequency transition point, 2nd motor
41527	Level of electronic thermal setting, 2nd motor
41528	Electronic thermal characteristic, 2nd motor
41529	Overload restriction operation mode, 2nd motor
4152A	Overload restriction level setting, 2nd motor
4152B	Deceleration rate at overload restriction, 2nd motor
4152C	Source of overload restriction selection, 2nd motor
41532	Terminal [1] function, 2nd motor
41533	Terminal [2] function, 2nd motor
41534	Terminal [3] function, 2nd motor
41535	Terminal [4] function, 2nd motor
41536	Terminal [5] function, 2nd motor
4153A	Overload level setting, 2nd motor
41541	Motor capacity, 2nd motor
41542	Motor poles setting, 2nd motor
41544	Motor stabilization constant, 2nd motor
[SigDataEnd]