﻿//E5ZN
MaxSigCnt=209
DataFormat=Hex

[C0-SigData]
C00000	CH1  PV
C00001	CH1  Status
C00002	CH1  Internal SP
C00003	CH1  Heater current value monitor
C00004	CH1  MV monitor for heating
C00005	CH1  MV monitor for cooling
C00006	CH1  PV hold value
C00100	CH2  PV
C00101	CH2  Status
C00102	CH2  Internal SP
C00103	CH2  Heater current value monitor
C00104	CH2  MV monitor for heating
C00105	CH2  MV monitor for cooling
C00106	CH2  PV hold value
[C0-SigDataEnd]

[C1-SigData]
C10000	Operation/adjustment protection
C10001	Initial setting/communications protection
C10002	Setup change protection
C10003	CH1  SP
C10004	CH1  Alarm value 1
C10005	CH1  Alarm upper limit value 1
C10006	CH1  Alarm lower limit value 1
C10007	CH1  Alarm value 2
C10008	CH1  Alarm upper limit value 2
C10009	CH1  Alarm lower limit value 2
C1000A	CH1  Alarm value 3
C1000B	CH1  Manual manipulated value
C1000C	CH1  Heater burnout detection
C1000D	CH1  SP 0
C1000E	CH1  SP 1
C1000F	CH1  Temperature input offset value
C10010	CH1  Upper limit temperature input offset value
C10011	CH1  Lower limit temperature input offset value
C10012	CH1  Proportional band
C10013	CH1  Integral time
C10014	CH1  Derivative time
C10015	CH1  Cooling coefficient
C10016	CH1  Dead band
C10017	CH1  Manual reset value
C10018	CH1  Heating hysteresis
C10019	CH1  Cooling hysteresis
C10100	Operation/adjustment protection
C10101	Initial setting/communications protection
C10102	Setup change protection
C10103	CH2  SP
C10104	CH2  Alarm value 1
C10105	CH2  Alarm upper limit value 1
C10106	CH2  Alarm lower limit value 1
C10107	CH2  Alarm value 2
C10108	CH2  Alarm upper limit value 2
C10109	CH2  Alarm lower limit value 2
C1010A	CH2  Alarm value 3
C1010B	CH2  Manual manipulated value
C1010C	CH2  Heater burnout detection
C1010D	CH2  SP 0
C1010E	CH2  SP 1
C1010F	CH2  Temperature input offset value
C10110	CH2  Upper limit temperature input offset value
C10111	CH2  Lower limit temperature input offset value
C10112	CH2  Proportional band
C10113	CH2  Integral time
C10114	CH2  Derivative time
C10115	CH2  Cooling coefficient
C10116	CH2  Dead band
C10117	CH2  Manual reset value
C10118	CH2  Heating hysteresis
C10119	CH2  Cooling hysteresis
[C1-SigDataEnd]

[C3-SigData]
C30000	Input type
C30001	CH1  Scaling upper limit
C30002	CH1  Scaling lower limit
C30003	CH1  Decimal point position
C30004	Temperature units
C30005	CH1  SP upper limit
C30006	CH1  SP lower limit
C30007	CH1  PID/OnOff
C30008	CH1  Heating control period
C30009	CH1  Cooling control period
C3000A	CH1  Direct/reverse operation
C3000B	CH1  Alarm 1 type
C3000C	CH1  Alarm 2 type
C3000D	CH1  Alarm 3 type
C3000E	Control output 1 allocation
C3000F	Control output 2 allocation
C30010	Auxiliary output 1 allocation
C30011	Auxiliary output 2 allocation
C30012	Operation after power ON
C30013	Communications data length
C30014	Communications stop bit
C30015	Communications parity
C30016	Communications response transmission wait time
C30017	No. of multi-SP uses
C30018	Event input function
C30019	Use multi-SP
C3001A	CH1  SP ramp setting
C3001B	Standby sequence restart
C3001C	CH1  Alarm 1 open in alarm
C3001D	CH1  Alarm 1 hysteresis
C3001E	CH1  Alarm 2 open in alarm
C3001F	CH1  Alarm 2 hysteresis
C30020	CH1  Alarm 3 open in alarm
C30021	CH1  Alarm 3 hysteresis
C30022	Use heater burnout
C30023	Heater burnout latch
C30024	CH1  Heater burnout hysteresis
C30025	Alpha
C30026	CH1  MV upper limit
C30027	CH1  MV lower limit
C30028	CH1  Input digital filter
C30029	Additional PV display
C3002A	Temperature input offset display add
C3002B	CH1  Alarm 1 latch
C3002C	CH1  Alarm 2 latch
C3002D	CH1  Alarm 3 latch
C3002E	Cold junction compensation method
C3002F	Auxiliary output 3 allocation
C30030	Auxiliary output 4 allocation
C30031	OUT1 transfer output upper limit
C30032	OUT1 transfer output lower limit
C30033	OUT2 transfer output upper limit
C30034	OUT2 transfer output lower limit 
C30035	SUB3 transfer output upper limit
C30036	SUB3 transfer output lower limit
C30037	SUB4 transfer output upper limit
C30038	SUB4 transfer output lower limit
C30039	Current output type
C3003A	Voltage output type
C3003B	Sensor error indicator
C3003C	Remote-local logic
C3003D	Input error output
C3003E	Input shift type
C30100	Input type
C30101	CH2  Scaling upper limit
C30102	CH2  Scaling lower limit
C30103	CH2  Decimal point position
C30104	Temperature units
C30105	CH2 SP upper limit
C30106	CH2 SP lower limit
C30107	CH2  PID/OnOff
C30108	CH2  Heating control period
C30109	CH2  Cooling control period
C3010A	CH2  Direct/reverse operation
C3010B	CH2  Alarm 1 type
C3010C	CH2  Alarm 2 type
C3010D	CH2  Alarm 3 type
C3010E	Control output 1 allocation
C3010F	Control output 2 allocation
C30110	Auxiliary output 1 allocation
C30111	Auxiliary output 2 allocation
C30112	Operation after power ON
C30113	Communications data length
C30114	Communications stop bit
C30115	Communications parity
C30116	Communications response transmission wait time
C30117	No. of multi-SP uses
C30118	Event input allocation
C30119	Use multi-SP
C3011A	CH2  SP ramp setting
C3011B	Standby sequence restart
C3011C	CH2  Alarm 1 open in alarm
C3011D	CH2  Alarm 1 hysteresis
C3011E	CH2  Alarm 2 open in alarm
C3011F	CH2  Alarm 2 hysteresis
C30120	CH2  Alarm 3 open in alarm
C30121	CH2  Alarm 3 hysteresis
C30122	Use heater burnout
C30123	Heater burnout latch
C30124	CH2  Heater burnout hysteresis
C30125	Alpha
C30126	CH2  MV upper limit
C30127	CH2  MV lower limit
C30128	CH2  Input digital filter
C30129	Additional PV display
C3012A	Temperature input offset display add
C3012B	CH2  Alarm 1 latch
C3012C	CH2  Alarm 2 latch
C3012D	CH2  Alarm 3 latch
C3012E	Cold junction compensation method
C3012F	Auxiliary output 3 allocation
C30130	Auxiliary output 4 allocation
C30131	OUT1 transfer output upper limit
C30132	OUT1 transfer output lower limit
C30133	OUT2 transfer output upper limit
C30134	OUT2 transfer output lower limit 
C30135	SUB3 transfer output upper limit
C30136	SUB3 transfer output lower limit
C30137	SUB4 transfer output upper limit
C30138	SUB4 transfer output lower limit
C30139	Current output type
C3013A	Voltage output type
C3013B	Sensor error indicator
C3013D	Input error output
C3013E	Input shift type
[C3-SigDataEnd]

[C5-SigData]
C50000	CH1  Remote PV
C50100	CH2  Remote PV
[C5-SigDataEnd]

[C7-SigData]
C70000	Remote PV mode
C70001	Remote PV communications wait time
C70100	Remote PV mode
C70101	Remote PV communications wait time
[C7-SigDataEnd]

[A-SigData]
A0000	Communications writing
A0001	RUN/STOP
A0002	Multi-SP
A0003	AT execute/cancel
A0004	Write mode
A0005	RAM data save
A0006	Software reset
A0007	Move to setting area 1
A0008	Move to protect level
A0009	Auto/manual
A000A	PV hold
A000B	Parameter initialize
A000C	Alarm latch cancel
[A-SigDataEnd]

[C0-SigData]-B
C00000	    CH1  PV
C00001.00  CH1  Current exceeded
C00001.01  CH1  Current hold
C00001.05  CH1  Indicate range exceeded
C00001.06  CH1  Input error
C00001.08  CH1  Heating output
C00001.09  CH1  Cooling output
C00001.10  CH1  HB output
C00001.12  CH1  Alarm output 1
C00001.13  CH1  Alarm output 2
C00001.14  CH1  Alarm output 3
C00001.16  CH1  Event input
C00001.20  CH1  Write mode
C00001.21  CH1  EEPROM
C00001.22  CH1  Setting area
C00001.23  CH1  AT execute/cancel
C00001.24  CH1  RUN/STOP
C00001.25  CH1  Data writing
C00001.26  CH1  Auto/manual
C00002	    CH1  Internal SP
C00003	    CH1  Heater current value monitor
C00004	    CH1  MV monitor for heating
C00005	    CH1  MV monitor for cooling
C00006 	    CH1  PV hold value
C00100	    CH2  PV
C00101.00  CH2  Current exceeded
C00101.01  CH2  Current hold
C00101.05  CH2  Indicate range exceeded
C00101.06  CH2  Input error
C00101.08  CH2  Heating output
C00101.09  CH2  Cooling output
C00101.10  CH2  HB output
C00101.12  CH2  Alarm output 1
C00101.13  CH2  Alarm output 2
C00101.14  CH2  Alarm output 3
C00101.16  CH2  Event input
C00101.20  CH2  Write mode
C00101.21  CH2  EEPROM
C00101.22  CH2  Setting area
C00101.23  CH2  AT execute/cancel
C00101.24  CH2  RUN/STOP
C00101.25  CH2  Data writing
C00101.26  CH2  Auto/manual
C00102	    CH2  Internal SP
C00103	    CH2  Heater current value monitor
C00104	    CH2  MV monitor for heating
C00105	    CH2  MV monitor for cooling
C00106	    CH2  PV hold value
[C0-SigDataEnd]-B