﻿﻿Name=PLC1
FB
MaxSigCnt=314
DataFormat=Hex

[SigData]
0000	Measured value (PV) monitor
0001	Current transformer 1 (CT1) input value monitor
0002	Current transformer 2 (CT2) input value monitor
0003	Set value (SV) monitor
0004	Remote setting (RS) input value monitor
0005	Burnout state monitor
0006	Burnout state monitor of feedback resistance input
0007	Event 1 state monitor
0008	Event 2 state monitor
0009	Event 3 state monitor
000A	Event 4 state monitor
000B	Heater break alarm 1 (HBA1) state monitor
000C	Heater break alarm 2 (HBA2) state monitor
000D	Manipulated output value (MV1) monitor [heat-side]
000E	Manipulated output value (MV2) monitor [cool-side]
000F	Error code
000F.0	Adjustment data error
000F.1	Back-up error
000F.2	A/D conversion error
000F.5	Custom data error
000F.7	Watchdog timer error
000F.8	Program error (stack)
000F.B	Program error (busy)
0010	Digital input (DI) state monitor
0010.0	The state of DI1
0010.1	The state of DI2
0010.2	The state of DI3
0010.3	The state of DI4
0010.4	The state of DI5
0010.5	The state of DI6
0010.6	The state of DI7
0011	Output state monitor
0011.0	The state of OUT1
0011.1	The state of OUT2
0011.2	The state of DO1
0011.3	The state of DO2
0011.4	The state of DO3
0011.5	The state of DO4
0012	Operation mode state monitor
0012.0	Control STOP
0012.1	Control RUN
0012.2	Manual mode
0012.3	Remote mode
0013	Memory area soak time monitor
0014	Integrated operating time monitor
0015	Holding peak value ambient temperature monitor
0016	Power feed forward input value monitor
0017	Backup memory state monitor
0020	PID/AT transfer
0021	Auto/Manual transfer
0022	Remote/Local transfer
0023	RUN/STOP transfer
0024	Memory area transfer
0025	Interlock release
0026	Event 1 set value (EV1)
0027	Event 2 set value (EV2)
0028	Event 3 set value (EV3)
0029	Event 4 set value (EV4)
002A	Control loop break alarm (LBA) time
002B	LBA deadband
002C	Set value (SV)
002D	Proportional band [heat-side]
002E	Integral time [heat-side]
002F	Derivative time [heat-side]
0030	Control response parameter
0031	Proportional band [cool-side]
0032	Integral time [cool-side]
0033	Derivative time [cool-side]
0034	Overlap/Deadband
0035	Manual reset
0036	Setting change rate limiter (up)
0037	Setting change rate limiter (down)
0038	Area soak time
0039	Link area number
003A	Heater break alarm 1 (HBA1) set value
003B	Heater break determination point 1
003C	Heater melting determination point 1
003D	Heater break alarm 2 (HBA2) set value
003E	Heater break determination point 2
003F	Heater melting determination point 2
0040	PV bias
0041	PV digital filter
0042	PV ratio
0043	PV low input cut-off
0044	RS bias
0045	RS digital filter
0046	RS ratio
0047	Proportional cycle time [heat-side]
0048	Proportional cycle time [cool-side]
0049	Manual manipulated output value
004A	Set lock level
004A.0	Lock only setting items other than event set value(EV1 to EV4)
004A.1	Lock only event set value(EV1 to EV4)
004A.2	Lock only set value(SV)
004B	STOP display
004C	Bar graph display
004D	Bar graph display resolution
004E	Direct key 1
004F	Direct key 2
0050	Direct key 3
0051	Direct key type
0052	Input type
0053	Display unit
0054	Decimal point position
0055	Input scale high
0056	Input scale low
0057	Input error determination point (high)
0058	Input error determination point (low)
0059	TC input burnout direction
005A	Square root extraction
005B	Power supply frequency
005C	Sampling cycle
005D	Remote setting input type
005E	Digital input (DI) assignment
005F	Output assignment
0060	Timer 1
0061	Timer 2
0062	Timer 3
0063	Timer 4
0064	Energized/De-energized
0064.0	DO1
0064.1	DO2
0064.2	DO3
0064.3	DO4
0065	Alarm (ALM) lamp lighting condition 1
0065.0	Event 1
0065.1	Event 2
0065.2	Event 3
0065.3	Event 4
0066	Alarm (ALM) lamp lighting condition 2
0066.0	HBA 1
0066.1	HBA 2
0067	Output status at STOP mode
0067.0	Event function
0067.1	Transmission output
006E	Transmission output type
006F	Transmission output scale high
0070	Transmission output scale low
0071	Event 1 type
0072	Event 1 hold action
0073	Event 1 interlock
0074	Event 1 differential gap
0075	Event 1 delay timer
0076	Event 1 action at input error
0076.0	Event 1 output turned on at input error occurrence
0076.1	Event 1 output turned on when an input error occurs in manual mode
0076.2	Event 1 output turned on when an input error occurs while the autotuning (AT) function is being executed
0076.3	Event 1 output turned on when an input error occurs while the setting change rate limiter is being operated
0077	Event 2 type
0078	Event 2 hold action
0079	Event 2 interlock
007A	Event 2 differential gap
007B	Event 2 delay timer
007C	Event 2 action at input error
007C.0	Event 2 output turned on at input error occurrence
007C.1	Event 2 output turned on when an input error occurs in manual mode
007C.2	Event 2 output turned on when an input error occurs while the autotuning (AT) function is being executed
007C.3	Event 2 output turned on when an input error occurs while the setting change rate limiter is being operated
007D	Event 3 type
007E	Event 3 hold action
007F	Event 3 interlock
0080	Event 3 differential gap
0081	Event 3 delay timer
0082	Event 3 action at input error
0082.0	Event 3 output turned on at input error occurrence
0082.1	Event 3 output turned on when an input error occurs in manual mode
0082.2	Event 3 output turned on when an input error occurs while the autotuning (AT) function is being executed
0082.3	Event 3 output turned on when an input error occurs while the setting change rate limiter is being operated
0083	Event 4 type
0084	Event 4 hold action
0085	Event 4 interlock
0086	Event 4 differential gap
0087	Event 4 delay timer
0088	Event 4 action at input error
0088.0	Event output turned on at input error occurrence
0088.1	Event output turned on when an input error occurs in manual mode
0088.2	Event output turned on when an input error occurs while the autotuning (AT) function is being executed
0088.3	Event output turned on when an input error occurs while the setting change rate limiter is being operated
0089	CT1 ratio
008A	CT1 assignment
008B	Heater break alarm 1 (HBA1) type
008C	Number of heater break alarm 1 (HBA1) delay times
008D	CT2 ratio
008E	CT2 assignment
008F	Heater break alarm 2 (HBA2) type
0090	Number of heater break alarm 2 (HBA2) delay times
0091	Hot/Cold start
0092	Start determination point
0093	External input type
0094	Master channel selection
0095	SV tracking
0096	MV transfer function
0097	Control action
0098	Integral/derivative time decimal point position
0099	Derivative term operating factor
009A	Undershoot suppression factor
009B	Derivative gain
009C	ON/OFF action differential gap (upper)
009D	ON/OFF action differential gap (lower)
009E	Action (high) at input error
009F	Action (low) at input error
00A0	Manipulated output value at input error
00A1	Manipulated output value (MV1) at STOP mode
00A2	Manipulated output value (MV2) at STOP mode
00A3	Output change rate limiter (up) [MV1]
00A4	Output change rate limiter (down) [MV1]
00A5	Output limiter (high) [MV1]
00A6	Output limiter (low) [MV1]
00A7	Output change rate limiter (up) [MV2]
00A8	Output change rate limiter (down) [MV2]
00A9	Output limiter (high) [MV2]
00AA	Output limiter (low) [MV2]
00AB	Power feed forward selection
00AC	Power feed forward gain
00AD	AT bias
00AE	AT cycles
00AF	Output value with AT turned on
00B0	Output value with AT turned off
00B1	AT differential gap time
00B2	Proportional band adjusting factor [heat-side]
00B3	Integral time adjusting factor [heat-side]
00B4	Derivative time adjusting factor [heat-side]
00B5	Proportional band adjusting factor [cool-side]
00B6	Integral time adjusting factor [cool-side]
00B7	Derivative time adjusting factor [cool-side]
00B8	Proportional band limiter (high) [heat-side]
00B9	Proportional band limiter (low) [heat-side]
00BA	Integral time limiter (high) [heat-side]
00BB	Integral time limiter (low) [heat-side]
00BC	Derivative time limiter (high) [heat-side]
00BD	Derivative time limiter (low) [heat-side]
00BE	Proportional band limiter (high) [cool-side]
00BF	Proportional band limiter (low) [cool-side]
00C0	Integral time limiter (high) [cool-side]
00C1	Integral time limiter (low) [cool-side]
00C2	Derivative time limiter (high) [cool-side]
00C3	Derivative time limiter (low) [cool-side]
00C4	Open/Close output neutral zone
00C5	Open/Close output differential gap
00C6	Action at feedback resistance (FBR) input error
00C7	Feedback adjustment
00C8	Control motor time
00C9	Integrated output limiter
00CA	Valve action at STOP
00CB	Startup tuning (ST)
00CC	ST proportional band adjusting factor
00CD	ST integral time adjusting factor
00CE	ST derivative time adjusting factor
00CF	ST start condition
00D0	Automatic temperature rise group
00D1	Automatic temperature rise learning
00D2	Automatic temperature rise dead time
00D3	Automatic temperature rise gradient data
00D4	RUN/STOP group
00D5	Setting change rate limiter unit time
00D6	Soak time unit
00D7	Setting limiter (high)
00D8	Setting limiter (low)
00D9	PV transfer function
00DA	PV flashing display at input error
00DA.0	Input error
0500	Setting memory area number
0501	Event 1 set value (EV1)
0502	Event 2 set value (EV2)
0503	Event 3 set value (EV3)
0504	Event 4 set value (EV4)
0505	Control loop break alarm (LBA) time
0506	LBA deadband
0507	Set value (SV)
0508	Proportional band[heat-side]
0509	Integral time[heat-side]
050A	Derivative time[heat-side]
050B	Control response parameter
050C	Proportional band 2[cool-side]
050D	Integral time[cool-side]
050E	Derivative time[cool-side]
050F	Overlap/Deadband
0510	Manual reset
0511	Setting change rate limiter(up)
0512	Setting change rate limiter(down)
0513	Area soak time
0514	Link area number
1000	Register address setting 1 Read/write address: 1500H
1001	Register address setting 2 Read/write address: 1501H
1002	Register address setting 3 Read/write address: 1502H
1003	Register address setting 4 Read/write address: 1503H
1004	Register address setting 5 Read/write address: 1504H
1005	Register address setting 6 Read/write address: 1505H
1006	Register address setting 7 Read/write address: 1506H
1007	Register address setting 8 Read/write address: 1507H
1008	Register address setting 9 Read/write address: 1508H
1009	Register address setting 10 Read/write address: 1509H
100A	Register address setting 11 Read/write address: 150AH
100B	Register address setting 12 Read/write address: 150BH
100C	Register address setting 13 Read/write address: 150CH
100D	Register address setting 14 Read/write address: 150DH
100E	Register address setting 15 Read/write address: 150EH
100F	Register address setting 16 Read/write address: 150FH
1500	Data specified by register address setting 1 (1000H)
1501	Data specified by register address setting 2 (1001H)
1502	Data specified by register address setting 3 (1002H)
1503	Data specified by register address setting 4 (1003H)
1504	Data specified by register address setting 5 (1004H)
1505	Data specified by register address setting 6 (1005H)
1506	Data specified by register address setting 7 (1006H)
1507	Data specified by register address setting 8 (1007H)
1508	Data specified by register address setting 9 (1008H)
1509	Data specified by register address setting 10 (1009H)
150A	Data specified by register address setting 11 (100AH)
150B	Data specified by register address setting 12 (100BH)
150C	Data specified by register address setting 13 (100CH)
150D	Data specified by register address setting 14 (100DH)
150E	Data specified by register address setting 15 (100EH)
150F	Data specified by register address setting 16 (100FH)
[SigDataEnd]