﻿Name=PLC1
FB
MaxSigCnt=208
DataFormat=Hex

[SigData]
00	M1	Measured value (PV) monitor
01	M3	Current transformer 1 (CT1) input value monitor
02	M4	Current transformer 2 (CT2) input value monitor
03	MS	Set value (SV) monitor
04	S2	Remote setting (RS) input value monitor
05	B1	Burnout state monitor
06	B2	Burnout state monitor of feedback resistance input
07	AA	Event 1 state monitor
08	AB	Event 2 state monitor
09	AC	Event 3 state monitor
0A	AD	Event 4 state monitor
0B	AE	Heater break alarm 1 (HBA1) state monitor
0C	AF	Heater break alarm 2 (HBA2) state monitor
0D	O1	Manipulated output value (MV1) monitor [heat-side]
0E	O2	Manipulated output value (MV2) monitor [cool-side]
0F	ER	Error code
0F.00	ER	Adjustment data error
0F.01	ER	Back-up error
0F.02	ER	A/D conversion error
0F.05	ER	Custom data error
0F.07	ER	Watchdog timer error
0F.08	ER	Program error (stack)
0F.0B	ER	Program error (busy)
10	L1	Digital input (DI) state monitor
10.00	L1	The state of DI1
10.01	L1	The state of DI2
10.02	L1	The state of DI3
10.03	L1	The state of DI4
10.04	L1	The state of DI5
10.05	L1	The state of DI6
10.06	L1	The state of DI7
11	Q1	Output state monitor
11.00	Q1	The state of OUT1
11.01	Q1	The state of OUT2
11.02	Q1	The state of DO1
11.03	Q1	The state of DO2
11.04	Q1	The state of DO3
11.05	Q1	The state of DO4
12	L0	Operation mode state monitor
12.00	L0	Control STOP
12.01	L0	Control RUN
12.02	L0	Manual mode
12.03	L0	Remote mode
13	TR	Memory area soak time monitor
14	UT	Integrated operating time monitor
15	Hp	Holding peak value ambient temperature monitor
16	HM	Power feed forward input value monitor
17	EM	Backup memory state monitor
18	VR	ROM version monitor (1-4 character)
19	G1	PID/AT transfer
1A	J1	Auto/Manual transfer
1B	C1	Remote/Local transfer
1C	SR	RUN/STOP transfer
1D	ZA	Memory area transfer
1E	IL	Interlock release
1F	A1	Event 1 set value (EV1)
20	A2	Event 2 set value (EV2)
21	A3	Event 3 set value (EV3)
22	A4	Event 4 set value (EV4)
23	A5	Control loop break alarm (LBA) time
24	N1	LBA deadband
25	S1	Set value (SV)
26	P1	Proportional band [heat-side]
27	I1	Integral time [heat-side]
28	D1	Derivative time [heat-side]
29	CA	Control response parameter
2A	P2	Proportional band [cool-side]
2B	I2	Integral time [cool-side]
2C	D2	Derivative time [cool-side]
2D	V1	Overlap/Deadband
2E	MR	Manual reset
2F	HH	Setting change rate limiter (up)
30	HL	Setting change rate limiter (down)
31	TM	Area soak time
32	LP	Link area number
33	A7	Heater break alarm 1 (HBA1) set value
34	NE	Heater break determination point 1
35	NF	Heater melting determination point 1
36	A8	Heater break alarm 2 (HBA2) set value
37	NH	Heater break determination point 2
38	NI	Heater melting determination point 2
39	PB	PV bias
3A	F1	PV digital filter
3B	PR	PV ratio
3C	DP	PV low input cut-off
3D	RB	RS bias
3E	F2	RS digital filter
3F	PR	RS ratio
40	T0	Proportional cycle time [heat-side]
41	T1	Proportional cycle time [cool-side]
42	ON	Manual manipulated output value
43	LK	Set lock level
43.00	LK	Lock only setting items other than SV and event set value(EV1 to EV4)
43.01	LK	Lock only event set value(EV1 to EV4)
43.02	LK	Lock only set value(SV)
44	DX	STOP display
45	DA	Bar graph display
46	DE	Bar graph display resolution
47	DK	Direct key 1
48	DL	Direct key 2
49	DM	Direct key 3
4A	DN	Direct key type
4B	XI	Input type
4C	PU	Display unit
4D	XU	Decimal point position
4E	XV	Input scale high
4F	XW	Input scale low
50	AV	Input error determination point (high)
51	AW	Input error determination point (low)
52	BS	TC input burnout direction
53	XH	Square root extraction
54	JT	Power supply frequency
55	TZ	Sampling cycle
56	XR	Remote setting input type
57	H2	Digital input (DI) assignment
58	E0	Output assignment
59	TH	Timer 1
5A	TI	Timer 2
5B	TJ	Timer 3
5C	TK	Timer 4
5D	NA	Energized/De-energized
5D.00	NA	DO1
5D.01	NA	DO2
5D.02	NA	DO3
5D.03	NA	DO4
5E	LY	Alarm (ALM) lamp lighting condition 1
5E.00	LY	Event 1
5E.01	LY	Event 2
5E.02	LY	Event 3
5E.03	LY	Event 4
5F	LZ	Alarm (ALM) lamp lighting condition 2
5F.00	LZ	HBA 1
5F.01	LZ	HBA 2
60	SS	Output status at STOP mode
60.00	SS	Event function
60.01	SS	Transmission output
61	LA	Transmission output type
62	HV	Transmission output scale high
63	HW	Transmission output scale low
64	XA	Event 1 type
65	WA	Event 1 hold action
66	LF	Event 1 interlock
67	HA	Event 1 differential gap
68	TD	Event 1 delay timer
69	OA	Event 1 action at input error
69.00	OA	Event 1 output turned on at input error occurrence
69.01	OA	Event 1 output turned on when an input error occurs in manual mode
69.02	OA	Event 1 output turned on when an input error occurs while the autotuning (AT) function is being executed
69.03	OA	Event 1 output turned on when an input error occurs while the setting change rate limiter is being operated
6A	XB	Event 2 type
6B	WB	Event 2 hold action
6C	LG	Event 2 interlock
6D	HB	Event 2 differential gap
6E	TG	Event 2 delay timer
6F	OB	Event 2 action at input error
6F.00	OB	Event 2 output turned on at input error occurrence
6F.01	OB	Event 2 output turned on when an input error occurs in manual mode
6F.02	OB	Event 2 output turned on when an input error occurs while the autotuning (AT) function is being executed
6F.03	OB	Event 2 output turned on when an input error occurs while the setting change rate limiter is being operated
70	XC	Event 3 type
71	WC	Event 3 hold action
72	LH	Event 3 interlock
73	HC	Event 3 differential gap
74	TE	Event 3 delay timer
75	OC	Event 3 action at input error
75.00	OC	Event 3 output turned on at input error occurrence
75.01	OC	Event 3 output turned on when an input error occurs in manual mode
75.02	OC	Event 3 output turned on when an input error occurs while the autotuning (AT) function is being executed
75.03	OC	Event 3 output turned on when an input error occurs while the setting change rate limiter is being operated
76	XD	Event 4 type
77	WD	Event 4 hold action
78	LI	Event 4 interlock
79	HD	Event 4 differential gap
7A	TF	Event 4 delay timer
7B	OD	Event 4 action at input error
7B.00	OD	Event output turned on at input error occurrence
7B.01	OD	Event output turned on when an input error occurs in manual mode
7B.02	OD	Event output turned on when an input error occurs while the autotuning (AT) function is being executed
7B.03	OD	Event output turned on when an input error occurs while the setting change rate limiter is being operated
7C	XS	CT1 ratio
7D	ZF	CT1 assignment
7E	ND	Heater break alarm 1 (HBA1) type
7F	DH	Number of heater break alarm 1 (HBA1) delay times
80	XT	CT2 ratio
81	ZG	CT2 assignment
82	NG	Heater break alarm 2 (HBA2) type
83	DF	Number of heater break alarm 2 (HBA2) delay times
84	XN	Hot/Cold start
85	SX	Start determination point
86	KM	External input type
87	MC	Master channel selection
88	XL	SV tracking
89	OT	MV transfer function
8A	XE	Control action
8B	PK	Integral/derivative time decimal point position
8C	KA	Derivative term operating factor
8D	KB	Undershoot suppression factor
8E	DG	Derivative gain
8F	IV	ON/OFF action differential gap (upper)
90	IW	ON/OFF action differential gap (lower)
91	WH	Action (high) at input error
92	WL	Action (low) at input error
93	OE	Manipulated output value at input error
94	OF	Manipulated output value (MV1) at STOP mode
95	OG	Manipulated output value (MV2) at STOP mode
96	PH	Output change rate limiter (up) [MV1]
97	PL	Output change rate limiter (down) [MV1]
98	OH	Output limiter (high) [MV1]
99	OL	Output limiter (low) [MV1]
9A	PX	Output change rate limiter (up) [MV2]
9B	PY	Output change rate limiter (down) [MV2]
9C	OX	Output limiter (high) [MV2]
9D	OY	Output limiter (low) [MV2]
9E	PF	Power feed forward selection
9F	PZ	Power feed forward gain
A0	GB	AT bias
A1	G3	AT cycles
A2	OP	Output value with AT turned on
A3	OQ	Output value with AT turned off
A4	GH	AT differential gap time
A5	KC	Proportional band adjusting factor [heat-side]
A6	KD	Integral time adjusting factor [heat-side]
A7	KE	Derivative time adjusting factor [heat-side]
A8	KF	Proportional band adjusting factor [cool-side]
A9	KG	Integral time adjusting factor [cool-side]
AA	KH	Derivative time adjusting factor [cool-side]
AB	P6	Proportional band limiter (high) [heat-side]
AC	P7	Proportional band limiter (low) [heat-side]
AD	I6	Integral time limiter (high) [heat-side]
AE	I7	Integral time limiter (low) [heat-side]
AF	D6	Derivative time limiter (high) [heat-side]
B0	D7	Derivative time limiter (low) [heat-side]
B1	P8	Proportional band limiter (high) [cool-side]
B2	P9	Proportional band limiter (low) [cool-side]
B3	I8	Integral time limiter (high) [cool-side]
B4	I9	Integral time limiter (low) [cool-side]
B5	D8	Derivative time limiter (high) [cool-side]
B6	D9	Derivative time limiter (low) [cool-side]
B7	V2	Open/Close output neutral zone
B8	VH	Open/Close output differential gap
B9	SY	Action at feedback resistance (FBR) input error
BA	FV	Feedback adjustment
BB	TN	Control motor time
BC	OI	Integrated output limiter
BD	VS	Valve action at STOP
BE	ST	Startup tuning (ST)
BF	KI	ST proportional band adjusting factor
C0	KJ	ST integral time adjusting factor
C1	KK	ST derivative time adjusting factor
C2	SU	ST start condition
C3	Y7	Automatic temperature rise group
C4	Y8	Automatic temperature rise learning
C5	RT	Automatic temperature rise dead time
C6	R2	Automatic temperature rise gradient data
C7	GQ	RUN/STOP group
C8	HU	Setting change rate limiter unit time
C9	RU	Soak time unit
CA	SH	Setting limiter (high)
CB	SL	Setting limiter (low)
CC	TS	PV transfer function
CD	DU	PV flashing display at input error
CD.00	DU	Input error
CE	VR	ROM version monitor (1-4 character)
CF	VR	ROM version monitor (5-8 character)
[SigDataEnd]