﻿﻿Name=Inverter
J1000
MaxSigCnt=0
DataFormat=Hex

[SigData]
0001	Operation signal
0002	Frequency Reference
0007	Analog output setting (10 V/4000 H)
0009	Multi-function contact output setting
000F	Reference selection settings
0020	Inverter status 1
0021	Error details 1
0022	Data link status
0023	Frequency reference (U1-01) (The unit can be set by H5-13)
0024	Output frequency (U1-02) (The unit can be set by H5-13)
0025	Output voltage reference (U1-06) (Unit: 0.1V)
0026	Output current (U1-03) (Unit: 0.01A)
0029	Error details 2
002A	Alarm Contents1
002B	Input Terminal Status (U1-10)
002C	Inverter status 2
002D	Output Terminal Status (U1-11)
0031	Main circuit current voltage (U1-07)(Unit: 1V)
0034	Production code1 [ASCII], Production type(J1000 = J0)
003D	Communications error details
003F	Output frequency
007F	Minor fault code
0098	Cumulative operation high (U4-01)
0099	Cumulative operation low (U4-01)
00AB	Inverter rated current (Unit: 0.01A)
00B6	The output frequency after soft start
00B8	Frequency Reference monitor
00BF	Operation error (oPE☐☐) Number
00C0	Fault Content 1
00C1	Fault Content 2
00C2	Fault Content 3
00C4	Fault Content 5
00C8	Minor fault content 2
00C9	Minor fault content 3
00CB	Minor fault content 5
00D0	CPF Content 1
00D1	CPF Content 2
0900	Write parameter data to EEPROM
0101	A1-01	Access Level Selection
0103	A1-03	Initialize
0104	A1-04	Password
0105	A1-05	Password setting
0180	b1-01	Frequency Reference Selection
0181	b1-02	Run Command Selection
0182	b1-03	Stopping method selection
0183	b1-04	Reverse Operation Selection
0186	b1-07	LOCAL/REMOTE Run Selection
0187	b1-08	Run Command selection in programming modes
01C3	b1-14	Phase Order Selection
01C6	b1-17	Run Command at Power Up
018A	b2-02	DC Injection Braking Current
018B	b2-03	DC Injection Braking Time/DC Excitation Time at Start
018C	b2-04	DC Injection Braking Time at Stop
0200	C1-01	Acceleration Time 1
0201	C1-02	Deceleration Time 1
0202	C1-03	Acceleration Time 2
0203	C1-04	Deceleration Time 2
0208	C1-09	Fast-Stop Time
020B	C2-01	S-Curve Characteristic at Accel Start
020C	C2-02	S-Curve Characteristic at Accel End
020D	C2-03	S-Curve Characteristic at Decel Start
020E	C2-04	S-Curve Characteristic at Decel Ends
020F	C3-01	Slip Compensation Gain
0210	C3-02	Slip Compensation Primary Delay Time
0215	C4-01	Torque Compensation Gain
0223	C6-01	Normal/Heavy Duty Selection
0224	C6-02	Carrier Frequency Selection
0225	C6-03	Carrier Frequency Upper Limit
0226	C6-04	Carrier Frequency Lower Limit
0227	C6-05	Carrier Frequency Proportional Gain
0280	d1-01	Frequency Reference 1
0281	d1-02	Frequency Reference 2
0282	d1-03	Frequency Reference 3
0283	d1-04	Frequency Reference 4
0284	d1-05	Frequency Reference 5
0285	d1-06	Frequency Reference 6
0286	d1-07	Frequency Reference 7
0287	d1-08	Frequency Reference 8
0292	d1-17	Jog Frequency Reference
0289	d2-01	Frequency Reference Upper Limit
028A	d2-02	Frequency Reference Lower Limit
0294	d3-01	Jump Frequency 1
0295	d3-02	Jump Frequency 2
0297	d3-04	Jump Frequency width
0298	d4-01	Frequency Reference Hold Function Selection
0300	E1-01	Input Voltage Setting
0302	E1-03	V/f Pattern Selection
0303	E1-04	Max Output Frequency
0304	E1-05	Max Output Voltage
0305	E1-06	Base Frequency
0306	E1-07	Mid Output Frequency
0307	E1-08	Mid Output Frequency Voltage
0308	E1-09	Minimum Output Freq.
0309	E1-10	Minimum Output Freq. Voltage
030E	E2-01	Motor Rated Current
030F	E2-02	Motor Rated Slip
0310	E2-03	Motor No-Load Current
0312	E2-05	Motor Line-to-Line Resistance
0438	H1-01	Multi-Function Digital Input Terminal S1 Function Selection
0439	H1-02	Multi-Function Digital Input Terminal S2 Function Selection
0400	H1-03	Multi-Function Digital Input Terminal S3 Function Selection
0401	H1-04	Multi-Function Digital Input Terminal S4 Function Selection
0402	H1-05	Multi-Function Digital Input Terminal S5 Function Selection
040B	H2-01	Terminal MA, MB and MC Function Selection (relay)
0410	H3-01	Terminal A1 Signal Level Selection
0411	H3-03	Terminal A1 Gain Setting
0412	H3-04	Terminal A1 Bias Setting
041B	H3-13	Analog Input Filter Time Constant
041D	H4-01	Multi-Function Analog Output Terminal AM
041E	H4-02	Multi-Function Analog Output Terminal AM Gain
041F	H4-03	Multi-Function Analog Output Terminal AM Bias
0425	H5-01	Slave Address
0426	H5-02	Communication Speed Selection
0427	H5-03	Communication Parity Selection
0428	H5-04	Stopping Method After Communication Error
0429	H5-05	Communication Fault Detection Selection
042A	H5-06	Drive Transmit Wait Time
042B	H5-07	RTS Control Selection
043D	H5-12	Run Command Method Selection
043E	H5-13	MEMOBUS Freq. Reference and Freq. Monitor Unit
0480	L1-01	Motor Overload Protection Selection
0481	L1-02	Motor Overload Protection Time
046D	L1-13	Continuous Electrothermal Operation Selection
0485	L2-01	Momentary Power Loss Operation Selection
048F	L3-01	Stall Prevention Selection during Acceleration
0490	L3-02	Stall Prevention Level during Acceleration
0492	L3-04	Stall Prevention Selection during Deceleration
0493	L3-05	Stall Prevention Selection during Run
0494	L3-06	Stall Prevention Level during Run
0499	L4-01	Speed Agreement Detection Level
0470	L4-07	Frequency Detection Conditions
049E	L5-01	Number of Auto Restart Attempts
04A1	L6-01	Torque Detection Selection
04A2	L6-02	Torque Detection Level
04A3	L6-03	Torque Detection Time
04AD	L8-01	Internal Dynamic Braking Resistor Protection Selection (ERF type)
04B1	L8-05	Input Phase Loss Protection Selection
04B6	L8-10	Heatsink Cooling Fan Operation Selection
04B8	L8-12	Ambient Temperature Setting
04BE	L8-18	Soft CLA Selection
04EC	L8-35	Installation Method Selection
04EF	L8-38	Carrier Frequency Reduction
0581	n1-02	Hunting Prevention Gain Setting
0531	n3-13	Overexcitation Deceleration Gain
0501	o1-02	User Monitor Selection After Power Up
0502	o1-03	Digital Operator Display Selection
0506	o2-02	STOP Key Function Selection
0508	o2-04	Drive Model Selection
0509	o2-05	Frequency Reference Setting Method Selection
050A	o2-06	LED Operation Selection when Digital Operator is Disconnected
050D	o2-09	Initialization mode
0515	o3-01	COPY function key
0516	o3-02	READ permission selection
050B	o4-01	Accumulated Operation Time Setting
050C	o4-02	Accumulated Operation Time Selection
050E	o4-03	Cooling Fan Operation Time Setting
051D	o4-05	Capacitor Maintenance Setting
0523	o4-07	Inrush Prevention Relay Maintenance Setting
0525	o4-09	IGBT Maintenance Setting
0510	o4-11	U2 Initialize Selection
0040	U1-01	Frequency Reference
0041	U1-02	Output Frequency
0042	U1-03	Output Current
0045	U1-06	Output Voltage Reference
0046	U1-07	DC Bus Voltage
0049	U1-10	Input Terminal Status
004A	U1-11	Output Terminal Status
004E	U1-13	Analog Input Terminal A1 Input monitor
0066	U1-19	MEMOBUS communication Error Code
004D	U1-25	Software No.(ROM)
005B	U1-26	Software No.(FLASH)
0080	U2-01	Current Fault
0081	U2-02	Previous Fault
004C	U4-01	Accumulated Operation Time
007E	U4-04	Cooling Fan Maintenance
007C	U4-05	Capacitor Maintenance
07D6	U4-06	Soft Charge Bypass Relay Maintenance
07D7	U4-07	IGBT Maintenance
0068	U4-08	Heatsink Temperature
005E	U4-09	LED Check
07CF	U4-13	Peak Hold Current
[SigDataEnd]

[SigData]-B
0001.0	H5-12 = 0: Forward Run Command (0 = Stop, 1 = Run) H5-12 = 1: Run Command (0 = Stop, 1 = Forward Run)
0001.1	H5-12 = 0: Reverse Run Command (0 = Stop, 1 = Run) H5-12 = 1: Forward/Reverse (0 = Stop, 1 = Reverse Run)
0001.2	External fault 1: Error (EFO)
0001.3	Fault reset 1: Reset command
0001.4	Multi-function input command 1
0001.5	Multi-function input command 2
0001.6	Multi-function input command 3
0001.7	Multi-function input command 4
0001.8	Multi-function input command 5
0002	Frequency Reference
0007	Analog output setting (10 V/4000 H)
0009.0	Contact output (Terminal MA/MB-MC) 1: ON 0: OFF
000F.C	Broadcast data terminal S5 input 1: Enabled 0: Disabled
0020.0	Operation 1: Operating 0: Stopped
0020.1	Reverse operation 1: Reverse operation 0: Forward operation
0020.2	Inverter startup complete 1: Completed 2: Not completed
0020.3	Error 1: Error
0020.4	Data setting error 1: Error
0020.5	Multi-function contact output (Terminal MA/MB-MC) 1: ON 0: OFF
0020.E	ComRef status
0020.F	ComCtrl status
0021.0	Overcurrent (oC)
0021.1	Main control circuit overvoltage (ov)
0021.2	Inverter overload (ol2)
0021.3	Inverter overheat (oH1)
0021.4	Braking Resistor Fault(rH)
0021.7	External Fault(EF0~5)
0021.8	Hardware Fault (includes OFx)
0021.9	Motor overload (oL1), Overtorque detection (oL3)
0021.B	Main circuit undervoltage (Uv) detected
0021.C	DC Bus Undervoltage(Uv1), Inrush Prevention Circuit Fault(Uv3)
0021.D	Main Circuit Voltage Fault (PF), Output Open-phase (LF)
0021.E	EMOBUS communications error(CE)
0021.F	Operator disconnected (oPr)
0022.0	1: Writing data
0022.3	1: Upper and lower limit errors
0022.4	1: Data integrity error
0022.5	1: EEPROM Writing data
0023	Frequency reference (U1-01) (The unit can be set by H5-13)
0024	Output frequency (U1-02) (The unit can be set by H5-13)
0025	Output voltage reference (U1-06) (Unit: 0.1V)
0026	Output current (U1-03) (Unit: 0.01A)
0029.2	DC Bus Voltage Fault(PF)
0029.3	Output Open-phase (LF)
0029.4	Braking Resistor Fault(rH)
002A.2	EF: Simultaneous Forward and Reverse Run Commands
002A.3	bb: Drive Baseblock
002A.4	oL3: Overtorque 1
002A.5	oH: Heatsink Overheat
002A.6	oV: DC Bus Overvoltage
002A.7	Uv: DC Bus Undervoltage
002A.9	CE: Communications Error
002B.0	1: Control circuit terminal S1 Closed
002B.1	1: Control circuit terminal S2 Closed
002B.2	1: Control circuit terminal S3 Closed
002B.3	1: Control circuit terminal S4 Closed
002B.4	1: Control circuit terminal S5 Closed
002C.0	Operation 1: Operating
002C.1	Zero-speed 1: Zero-speed
002C.2	Frequency matching 1: Matched
002C.3	User-defined speed matching 1: Matched
002C.4	Frequency detection 1 1: Output frequency≦L4-01
002C.5	Frequency detection 2 1: Output frequency≧L4-01
002C.6	Inverter startup completed 1: Startup completed
002C.7	Low voltage detection 1: Detected
002C.8	Baseblock 1: Inverter output baseblock
002C.9	Frequency reference mode 1: Not communications 0: Communications
002C.A	Run Command mode 1: Not communications 0: Communications
002C.B	Overtorque detection
002C.E	Error 1:Error occurred
002C.F	MEMOBUS communications time-out 1: Timed out
002D.0	Multi-function contact output (terminal MA/MB-MC) 1: ON 0: OFF
0031	Main circuit current voltage (U1-07)(Unit: 1V)
0034	Production code1 [ASCII], Production type(J1000 = J0)
003D.0	CRC error
003D.1	Invalid data length
003D.3	Parity error
003D.4	Overrun error
003D.5	Framing error
003D.6	Time-out
003F	Output frequency
007F	Minor fault code
0098	Cumulative operation high (U4-01)
0099	Cumulative operation low (U4-01)
00AB	Inverter rated current (Unit: 0.01A)
00B6	The output frequency after soft start
00B8	Frequency Reference monitor
00BF	Operation error (oPE☐☐) Number
00C0.1	DC Bus Undervoltage(Uv1)
00C0.3	Inrush Prevention Circuit Fault(Uv3)
00C0.6	Overcurrent (oC)
00C0.7	Main control circuit overvoltage (ov)
00C0.9	Heat sink overheating (oH1)
00C0.A	Motor overload (oL1)
00C0.B	Inverter overload (oL2)
00C0.C	Overtorque detection (oL3)
00C0.F	Braking Resistor Fault(rH)
00C1.0	External fault(Input Terminal S3) (EF3)
00C1.1	External fault(Input Terminal S4) (EF4)
00C1.2	External fault(Input Terminal S5) (EF5)
00C1.A	Main circuit voltage fault(PF)
00C1.D	Operator disconnected (oPr)
00C1.E	EEPROM Writing data error (Err)
00C2.0	MEMOBUS communication error (CE)
00C2.6	External fault detected in MEMOBUS communication option unit (EF0)
00C2.F	Hardware error (Err)
00C4.1	External fault(Input Terminal S1) (EF1)
00C4.2	External fault(Input Terminal S2) (EF2)
00C4.5	Current offset fault(CoF)
00C8.0	Main circuit undervoltage(Uv)
00C8.1	Main circuit overvoltage(Ov)
00C8.2	Heat sink overheating (oH)
00C8.4	Overtorque (oL3)
00C8.6	Input Forward and Reverse command at same time
00C8.7	Inverter base block (bb)
00C8.8	External fault(Input Terminal S3) (EF3)
00C8.9	External fault(Input Terminal S4) (EF4)
00C8.A	External fault(Input Terminal S5) (EF5)
00C9.2	Operator disconnected (oPr)
00C9.3	MEMOBUS communication error (CE)
00C9.5	Communication standby
00C9.6	Motor overload (oL1)
00C9.7	Inverter overload (oL2)
00CB.8	External fault(Input Terminal S1) (EF1)
00CB.9	External fault(Input Terminal S2) (EF2)
00D0.2	A/D converter fault (CPF02)
00D0.6	EEPROM data fault (CPF06)
00D0.8	EEPROM serial communications fault (CPF08)
00D0.B	RAM  fault (CPF11)
00D0.C	Flash memory fault (CPF12)
00D0.E	The control circuit fault (CPF14)
00D1.1	Interrupt fault (CPF17)
00D1.2	The control circuit fault (CPF18)
00D1.6	A/D converter fault(CPF22)
00D1.7	PWM feedback data fault (CPF23)
00D1.8	Inverte capacity signal fault(CPF24)
0900	Write parameter data to EEPROM
0101	A1-01	Access Level Selection
0103	A1-03	Initialize
0104	A1-04	Password
0105	A1-05	Password setting
0180	b1-01	Frequency Reference Selection
0181	b1-02	Run Command Selection
0182	b1-03	Stopping method selection
0183	b1-04	Reverse Operation Selection
0186	b1-07	LOCAL/REMOTE Run Selection
0187	b1-08	Run Command selection in programming modes
01C3	b1-14	Phase Order Selection
01C6	b1-17	Run Command at Power Up
018A	b2-02	DC Injection Braking Current
018B	b2-03	DC Injection Braking Time/DC Excitation Time at Start
018C	b2-04	DC Injection Braking Time at Stop
0200	C1-01	Acceleration Time 1
0201	C1-02	Deceleration Time 1
0202	C1-03	Acceleration Time 2
0203	C1-04	Deceleration Time 2
0208	C1-09	Fast-Stop Time
020B	C2-01	S-Curve Characteristic at Accel Start
020C	C2-02	S-Curve Characteristic at Accel End
020D	C2-03	S-Curve Characteristic at Decel Start
020E	C2-04	S-Curve Characteristic at Decel Ends
020F	C3-01	Slip Compensation Gain
0210	C3-02	Slip Compensation Primary Delay Time
0215	C4-01	Torque Compensation Gain
0223	C6-01	Normal/Heavy Duty Selection
0224	C6-02	Carrier Frequency Selection
0225	C6-03	Carrier Frequency Upper Limit
0226	C6-04	Carrier Frequency Lower Limit
0227	C6-05	Carrier Frequency Proportional Gain
0280	d1-01	Frequency Reference 1
0281	d1-02	Frequency Reference 2
0282	d1-03	Frequency Reference 3
0283	d1-04	Frequency Reference 4
0284	d1-05	Frequency Reference 5
0285	d1-06	Frequency Reference 6
0286	d1-07	Frequency Reference 7
0287	d1-08	Frequency Reference 8
0292	d1-17	Jog Frequency Reference
0289	d2-01	Frequency Reference Upper Limit
028A	d2-02	Frequency Reference Lower Limit
0294	d3-01	Jump Frequency 1
0295	d3-02	Jump Frequency 2
0297	d3-04	Jump Frequency width
0298	d4-01	Frequency Reference Hold Function Selection
0300	E1-01	Input Voltage Setting
0302	E1-03	V/f Pattern Selection
0303	E1-04	Max Output Frequency
0304	E1-05	Max Output Voltage
0305	E1-06	Base Frequency
0306	E1-07	Mid Output Frequency
0307	E1-08	Mid Output Frequency Voltage
0308	E1-09	Minimum Output Freq.
0309	E1-10	Minimum Output Freq. Voltage
030E	E2-01	Motor Rated Current
030F	E2-02	Motor Rated Slip
0310	E2-03	Motor No-Load Current
0312	E2-05	Motor Line-to-Line Resistance
0438	H1-01	Multi-Function Digital Input Terminal S1 Function Selection
0439	H1-02	Multi-Function Digital Input Terminal S2 Function Selection
0400	H1-03	Multi-Function Digital Input Terminal S3 Function Selection
0401	H1-04	Multi-Function Digital Input Terminal S4 Function Selection
0402	H1-05	Multi-Function Digital Input Terminal S5 Function Selection
040B	H2-01	Terminal MA, MB and MC Function Selection (relay)
0410	H3-01	Terminal A1 Signal Level Selection
0411	H3-03	Terminal A1 Gain Setting
0412	H3-04	Terminal A1 Bias Setting
041B	H3-13	Analog Input Filter Time Constant
041D	H4-01	Multi-Function Analog Output Terminal AM
041E	H4-02	Multi-Function Analog Output Terminal AM Gain
041F	H4-03	Multi-Function Analog Output Terminal AM Bias
0425	H5-01	Slave Address
0426	H5-02	Communication Speed Selection
0427	H5-03	Communication Parity Selection
0428	H5-04	Stopping Method After Communication Error
0429	H5-05	Communication Fault Detection Selection
042A	H5-06	Drive Transmit Wait Time
042B	H5-07	RTS Control Selection
043D	H5-12	Run Command Method Selection
043E	H5-13	MEMOBUS Freq. Reference and Freq. Monitor Unit
0480	L1-01	Motor Overload Protection Selection
0481	L1-02	Motor Overload Protection Time
046D	L1-13	Continuous Electrothermal Operation Selection
0485	L2-01	Momentary Power Loss Operation Selection
048F	L3-01	Stall Prevention Selection during Acceleration
0490	L3-02	Stall Prevention Level during Acceleration
0492	L3-04	Stall Prevention Selection during Deceleration
0493	L3-05	Stall Prevention Selection during Run
0494	L3-06	Stall Prevention Level during Run
0499	L4-01	Speed Agreement Detection Level
0470	L4-07	Frequency Detection Conditions
049E	L5-01	Number of Auto Restart Attempts
04A1	L6-01	Torque Detection Selection
04A2	L6-02	Torque Detection Level
04A3	L6-03	Torque Detection Time
04AD	L8-01	Internal Dynamic Braking Resistor Protection Selection (ERF type)
04B1	L8-05	Input Phase Loss Protection Selection
04B6	L8-10	Heatsink Cooling Fan Operation Selection
04B8	L8-12	Ambient Temperature Setting
04BE	L8-18	Soft CLA Selection
04EC	L8-35	Installation Method Selection
04EF	L8-38	Carrier Frequency Reduction
0581	n1-02	Hunting Prevention Gain Setting
0531	n3-13	Overexcitation Deceleration Gain
0501	o1-02	User Monitor Selection After Power Up
0502	o1-03	Digital Operator Display Selection
0506	o2-02	STOP Key Function Selection
0508	o2-04	Drive Model Selection
0509	o2-05	Frequency Reference Setting Method Selection
050A	o2-06	LED Operation Selection when Digital Operator is Disconnected
050D	o2-09	Initialization mode
0515	o3-01	COPY function key
0516	o3-02	READ permission selection
050B	o4-01	Accumulated Operation Time Setting
050C	o4-02	Accumulated Operation Time Selection
050E	o4-03	Cooling Fan Operation Time Setting
051D	o4-05	Capacitor Maintenance Setting
0523	o4-07	Inrush Prevention Relay Maintenance Setting
0525	o4-09	IGBT Maintenance Setting
0510	o4-11	U2 Initialize Selection
0040	U1-01	Frequency Reference
0041	U1-02	Output Frequency
0042	U1-03	Output Current
0045	U1-06	Output Voltage Reference
0046	U1-07	DC Bus Voltage
0049.0	U1-10	1: Digital input terminal S1 enabled
0049.1	U1-10	1: Digital input terminal S2 enabled
0049.2	U1-10	1: Digital input terminal S3 enabled
0049.3	U1-10	1: Digital input terminal S4 enabled
0049.4	U1-10	1: Digital input terminal S5 enabled
004A.0	U1-11	1: Multi-Function Digital Output (fault) (terminal MA/MB-MC)
004E	U1-13	Analog Input Terminal A1 Input monitor
0066.0	U1-19	1:CRC error 
0066.1	U1-19	1:Data length error
0066.3	U1-19	1:Parity error
0066.4	U1-19	1:Overrun error
0066.5	U1-19	1:Framing error
0066.6	U1-19	1:Timeout
004D	U1-25	Software No.(ROM)
005B	U1-26	Software No.(FLASH)
0080	U2-01	Current Fault
0081	U2-02	Previous Fault
004C	U4-01	Accumulated Operation Time
007E	U4-04	Cooling Fan Maintenance
007C	U4-05	Capacitor Maintenance
07D6	U4-06	Soft Charge Bypass Relay Maintenance
07D7	U4-07	IGBT Maintenance
0068	U4-08	Heatsink Temperature
005E	U4-09	LED Check
07CF	U4-13	Peak Hold Current
[SigDataEnd]-B