﻿﻿Name=Inverter
VS mini J7
MaxSigCnt=0
DataFormat=Hex

[SigData]
0001	Operation signal
0002	Frequency reference
0003	V/f gain (1000/100%), Setting range:2.0 to 200.0%
0020	Status Signal
0021	Fault Contents
0022	Data link status
0023	Frequency reference
0024	Output frequency
0027	Output current (10/1A)
0028	Output voltage reference (1/1V)
002B	Control Circuit Terminal Input Status
002C	Inverter status
002D	Control Circuit Terminal Output Status
0031	Main circuit DC voltage (1/1V)
003D	Contents of Communication Error
0900	ENTER command
0101	n01	Password
0102	n02	RUN Command Selection
0103	n03	Frequency Reference Selection
0104	n04	Stopping Method Selection
0105	n05	Reverse Run Prohibit
0106	n06	Stop Key Selection
0107	n07	Frequency Reference Selection in Local Mode
0108	n08	Frequency Reference Setting Method From Digital Operator
0109	n09	Max. Output Frequency
010A	n10	Max. Voltage
010B	n11	Max. Voltage Output Frequency
010C	n12	Mid. Output Frequency
010D	n13	Mid. Output Frequency Voltage
010E	n14	Min. Output Frequency
010F	n15	Min. Output Frequency Voltage
0110	n16	Acceleration Time 1
0111	n17	Deceleration Time 1
0112	n18	Acceleration Time 2
0113	n19	Deceleration Time 2
0114	n20	S-curve Selection
0115	n21	Frequency Reference 1 (Master Speed Frequency Reference)
0116	n22	Frequency Reference 2
0117	n23	Frequency Reference 3
0118	n24	Frequency Reference 4
0119	n25	Frequency Reference 5
011A	n26	Frequency Reference 6
011B	n27	Frequency Reference 7
011C	n28	Frequency Reference 8
011D	n29	Jog Frequency
011E	n30	Frequency Reference Upper Limit
011F	n31	Frequency Reference Lower Limit
0120	n32	Motor Rated Current
0121	n33	Electronic Thermal Motor Protection Selection
0122	n34	Electronic Thermal Motor Protection Time Constant Setting
0123	n35	Selecting Cooling Fan Operation
0124	n36	Multi-function Input Selection 2
0125	n37	Multi-function Input Selection 3
0126	n38	Multi-function Input Selection 4
0127	n39	Multi-function Input Selection 5
0128	n40	Multi-function Output Selection
0129	n41	Analog Frequency Reference Gain
012A	n42	Analog Frequency Reference Bias
012B	n43	Analog Frequency Reference Filter Time Constant
012C	n44	Multi-function Ana-log Output(terminal AM-AC)
012D	n45	Analog Monitor Gain
012E	n46	Carrier Frequency Selection
012F	n47	Momentary Power Loss Ridethrough Method
0130	n48	Automatic Retry Attempts
0131	n49	Jump Frequency 1
0132	n50	Jump Frequency 2
0133	n51	Jump Frequency Range
0134	n52	DC Injection Braking Current
0135	n53	DC Injection Braking Time at Stop
0136	n54	DC Injection Braking Time at Startup
0137	n55	Stall Prevention During Deceleration
0138	n56	Stall Prevention Level During Acceleration
0139	n57	Stall Prevention while Running
013A	n58	Frequency Detection Level
013B	n59	Overtorque Detection Function
013C	n60	Overtorque Detection Level
013D	n61	Overtorque Detection Time
013E	n62	Hold Output
013F	n63	Torque Compensation Gain
0140	n64	Motor Rated Slip
0141	n65	Motor No-load Current
0142	n66	Slip Compensation Gain
0143	n67	Slip Compensation Time Constant
0144	n68	MEMOBUS Timeover Detection Selection
0145	n69	MEMOBUS frequency reference and frequency monitor unit
0146	n70	MEMOBUS Slave Address
0147	n71	MEMOBUS BPS Selection
0148	n72	MEMOBUS Parity Selection
0149	n73	Transmission Waiting Time
014A	n74	RTS Control
014B	n75	Reducing Carrier Frequency Selection At Low Speed
014C	n76	Constant Copy Function Selection
014D	n77	Constant Read Selection Prohibit
014E	n78	Fault History
014F	n79	Software Version No.
[SigDataEnd]

[SigData]-B
0001.0	Run command 1: Run 0: Stop
0001.1	Reverse run 1: Reverse run 0: Forward run
0001.2	External fault 1: Error (EFO)
0001.3	Fault reset 1: Reset command
0001.5	Multi-function input reference 2 (Function selected by n36)
0001.6	Multi-function input reference 3 (Function selected by n37)
0001.7	Multi-function input reference 4 (Function selected by n38)
0001.8	Multi-function input reference 5 (Function selected by n39)
0002	Frequency reference
0003	V/f gain (1000/100%), Setting range:2.0 to 200.0%
0009.0	Multi-function output reference 1 1: MA "ON" (Effective when n040=18)
0020.0	Run command 1: Run 0: Stop
0020.1	Reverse run 1: Reverse run 0: Forward run
0020.2	Inverter operation ready 1: Ready 0: Not ready
0020.3	Fault 1: Fault
0020.4	Data setting error 1:Error
0020.5	Multi-function output 1 (1: MA ON)
0021.0	Overcurrent (OC)
0021.1	Overvoltage (OV) 
0021.2	Inverter overload (OL2) 
0021.3	Inverter overheat (OH1) 
0021.7	External fault (EF, EFO),Emergence stop (STP)
0021.8	Hardware fault (FXX) 
0021.9	Motor overload (OL1)
0021.A	Overtorque detection (OL3)
0021.C	Power loss (UV1)
0021.D	Grounding (GF)
0021.E	MEMOBUS communications timeover (CE)
0022.0	Data write in
0022.3	Upper/lower limit fault
0022.4	Consistency fault
0023	Frequency reference
0024	Output frequency
0027	Output current (10/1A)
0028	Output voltage reference (1/1V)
002B.0	Terminal S1 1: Closed
002B.1	Terminal S2 1: Closed
002B.2	Terminal S3 1: Closed
002B.3	Terminal S4 1: Closed
002B.4	Terminal S5 1: Closed
002C.0	Run 1:Run
002C.1	Zero-speed 1: Zero-speed
002C.2	Frequency agreed 1: Agreed
002C.3	Minor fault (Alarm is indicated.)
002C.4	Frequency detection 1 1: Output frequency ≤ (n58)
002C.5	Frequency detection 2 1: Output frequency ≥ (n58)
002C.6	Inverter operation ready 1:Ready
002C.7	Undervoltage detection 1: Undervoltage detection
002C.8	Baseblock 1: Inverter baseblock detection
002C.9	Frequency reference mode 1: Other than communications 0: Communications
002C.A	Run Command mode 1: Other than communications 0: Communications
002C.B	Overtorque detection 1: Overtorque detection
002C.D	Fault restart
002C.E	Fault (Including communications timeover) 1: Fault
002C.F	Communications timeover 1: Timeover
002D.0	MA "ON" 1: Closed
0031	Main circuit DC voltage (1/1V)
003D.0	CRC error
003D.1	Improper data length
003D.3	Parity error
003D.4	Overrun error
003D.5	Framing error
003D.6	Timeover
0900	ENTER command
0101	n01	Password
0102	n02	RUN Command Selection
0103	n03	Frequency Reference Selection
0104	n04	Stopping Method Selection
0105	n05	Reverse Run Prohibit
0106	n06	Stop Key Selection
0107	n07	Frequency Reference Selection in Local Mode
0108	n08	Frequency Reference Setting Method From Digital Operator
0109	n09	Max. Output Frequency
010A	n10	Max. Voltage
010B	n11	Max. Voltage Output Frequency
010C	n12	Mid. Output Frequency
010D	n13	Mid. Output Frequency Voltage
010E	n14	Min. Output Frequency
010F	n15	Min. Output Frequency Voltage
0110	n16	Acceleration Time 1
0111	n17	Deceleration Time 1
0112	n18	Acceleration Time 2
0113	n19	Deceleration Time 2
0114	n20	S-curve Selection
0115	n21	Frequency Reference 1 (Master Speed Frequency Reference)
0116	n22	Frequency Reference 2
0117	n23	Frequency Reference 3
0118	n24	Frequency Reference 4
0119	n25	Frequency Reference 5
011A	n26	Frequency Reference 6
011B	n27	Frequency Reference 7
011C	n28	Frequency Reference 8
011D	n29	Jog Frequency
011E	n30	Frequency Reference Upper Limit
011F	n31	Frequency Reference Lower Limit
0120	n32	Motor Rated Current
0121	n33	Electronic Thermal Motor Protection Selection
0122	n34	Electronic Thermal Motor Protection Time Constant Setting
0123	n35	Selecting Cooling Fan Operation
0124	n36	Multi-function Input Selection 2
0125	n37	Multi-function Input Selection 3
0126	n38	Multi-function Input Selection 4
0127	n39	Multi-function Input Selection 5
0128	n40	Multi-function Output Selection
0129	n41	Analog Frequency Reference Gain
012A	n42	Analog Frequency Reference Bias
012B	n43	Analog Frequency Reference Filter Time Constant
012C	n44	Multi-function Ana-log Output(terminal AM-AC)
012D	n45	Analog Monitor Gain
012E	n46	Carrier Frequency Selection
012F	n47	Momentary Power Loss Ridethrough Method
0130	n48	Automatic Retry Attempts
0131	n49	Jump Frequency 1
0132	n50	Jump Frequency 2
0133	n51	Jump Frequency Range
0134	n52	DC Injection Braking Current
0135	n53	DC Injection Braking Time at Stop
0136	n54	DC Injection Braking Time at Startup
0137	n55	Stall Prevention During Deceleration
0138	n56	Stall Prevention Level During Acceleration
0139	n57	Stall Prevention while Running
013A	n58	Frequency Detection Level
013B	n59	Overtorque Detection Function
013C	n60	Overtorque Detection Level
013D	n61	Overtorque Detection Time
013E	n62	Hold Output
013F	n63	Torque Compensation Gain
0140	n64	Motor Rated Slip
0141	n65	Motor No-load Current
0142	n66	Slip Compensation Gain
0143	n67	Slip Compensation Time Constant
0144	n68	MEMOBUS Timeover Detection Selection
0145	n69	MEMOBUS frequency reference and frequency monitor unit
0146	n70	MEMOBUS Slave Address
0147	n71	MEMOBUS BPS Selection
0148	n72	MEMOBUS Parity Selection
0149	n73	Transmission Waiting Time
014A	n74	RTS Control
014B	n75	Reducing Carrier Frequency Selection At Low Speed
014C	n76	Constant Copy Function Selection
014D	n77	Constant Read Selection Prohibit
014E	n78	Fault History
014F	n79	Software Version No.
[SigDataEnd]-B