﻿﻿Name=Inverter
VS mini V7
MaxSigCnt=0
DataFormat=Hex

[SigData]
0001	Operation signal
0002	Frequency Reference (unit: n152)
0003	V/f gain (1000/100%), Setting range:2.0 to 200.0%
0020	Status signal
0021	Fault description
0022	Data link status
0023	Frequency reference (unit: n152)
0024	Output frequency (unit: n152)
0027	Output current (10/1A)
0028	Output voltage reference (1/1V)
0029	Fault description
002A	Alarm description
002B	Sequence input status
002C	Inverter status
002D	Multi-function output status
002E	Inverter status
0031	Main circuit DC voltage (1/1V)
0032	Torque monitor (1/1 % ; 100 %/Motor rated torque ; with sign)
0037	Output Power (1/1 W: with sign)
0038	PID feedback value (100 % /Input equivalent to max. output frequency ;10/1 % ; without sign)
0039	PID input value (±100 %/±Max. output frequency ; 10/1 % ; with sign)
003A	PID output value (±100 %/±Max. output frequency ; 10/1 % ; with sign)
003D	Communications error details
0900	ENTER command
0101	n001	Password
0102	n002	Control Mode Selection(Note 6)
0103	n003	RUN Command Selection
0104	n004	Frequency Reference Selection
0105	n005	Stopping Method Selection
0106	n006	Reverse Run Prohibit
0107	n007	Stop Key Selection
0108	n008	Frequency Reference Selection in Local Mode
0109	n009	Frequency Reference Setting Method From Digital Operator
010A	n010	Detecting Fault Contact of Digital Operator
010B	n011	Max. Output Frequency
010C	n012	Max. Voltage
010D	n013	Max. Voltage Output Frequency
010E	n014	Mid. Output Frequency
010F	n015	Mid. Output Frequency Voltage
0110	n016	Min. Output Frequency
0111	n017	Min. Output Frequency Voltage
0112	n018	Selecting Setting Unit for Acceleration/deceleration Time
0113	n019	Acceleration Time 1
0114	n020	Deceleration Time 1
0115	n021	Acceleration Time 2
0116	n022	Deceleration Time 2
0117	n023	S-curve Selection
0118	n024	Frequency Reference 1 (Master Frequency Reference)
0119	n025	Frequency Reference 2
011A	n026	Frequency Reference 3
011B	n027	Frequency Reference 4
011C	n028	Frequency Reference 5
011D	n029	Frequency Reference 6
011E	n030	Frequency Reference 7
011F	n031	Frequency Reference 8
0120	n032	Jog Frequency
0121	n033	Frequency Reference Upper Limit
0122	n034	Frequency Reference Lower Limit
0123	n035	Setting/displaying Unit Selection for Frequency Reference
0124	n036	Motor Rated Current
0125	n037	Electronic Thermal Motor Protection Selection
0126	n038	Electronic Thermal Motor Protection Time Constant Setting
0127	n039	Selecting Cooling Fan Operation
0128	n040	Motor Rotation Direction
0129	n041	Acceleration Time 3
012A	n042	Deceleration Time 3
012B	n043	Acceleration Time 4
012C	n044	Deceleration Time 4
012D	n045	Frequency reference bias step amount (UP/DOWN command 2)
012E	n046	Frequency reference bias accel/decel rate (UP/DOWN command 2)
012F	n047	Frequency reference bias operation mode selection (UP/DOWN command 2)
0130	n048	Frequency reference bias value (UP/DOWN command 2)
0131	n049	Analog frequency reference fluctuation limit level (UP/DOWN command 2)
0132	n050	Multi-function Input Selection 1 (Terminal S1)
0133	n051	Multi-function Input Selection 2 (Terminal S2)
0134	n052	Multi-function Input Selection 3 (Terminal S3)
0135	n053	Multi-function Input Selection 4 (Terminal S4)
0136	n054	Multi-function Input Selection 5 (Terminal S5)
0137	n055	Multi-function Input Selection 6 (Terminal S6)
0138	n056	Multi-function Input Selection 7 (Terminal S7)
0139	n057	Multi-function Output Selection 1
013A	n058	Multi-function Output Selection 2
013B	n059	Multi-function Output Selection 3
013C	n060	Analog Frequency Reference Gain
013D	n061	Analog Frequency Reference Bias
013E	n062	Filter Time Constant for Analog Frequency Reference
013F	n063	Watchdog Error Operation Selection (For SI-T/V7)
0140	n064	Frequency Reference Loss Detection Selection
0141	n065	Monitor Output Type
0142	n066	Monitor Item Selection
0143	n067	Monitor Gain
0144	n068	Analog Frequency Reference Gain (Voltage input from Operator)
0145	n069	Analog Frequency Reference Bias (Voltage input from Operator)
0146	n070	Analog Frequency Reference Filter Time Constant (Voltage input from Operator)
0147	n071	Analog Frequency Reference Gain (Voltage input from Operator)
0148	n072	Analog Frequency Reference Bias (Current input from Operator)
0149	n073	Analog Frequency Reference Filter Time Constant (Current input from Operator)
014A	n074	Pulse Train Frequency Reference Gain
014B	n075	Pulse Train Frequency Reference Bias
014C	n076	Pulse Train Frequency Filter Time Constant
014D	n077	Multi-function Analog Input Function
014E	n078	Multi-function Analog Input Signal Selection
014F	n079	Frequency Reference Bias (FBIAS) Value
0150	n080	Carrier Frequency Selection
0151	n081	Momentary Power Loss Ridethrough Method
0152	n082	Automatic Retry Attempts
0153	n083	Jump Frequency 1
0154	n084	Jump Frequency 2
0155	n085	Jump Frequency 3
0156	n086	Jump Frequency Range
0157	n087	Cumulative operation time function selection
0158	n088	Cumulative operation time
0159	n089	DC Injection Braking Current
015A	n090	DC Injection Braking Time at Stop
015B	n091	DC Injection Braking Time at Startup
015C	n092	Stall Prevention During Deceleration
015D	n093	Stall Prevention Level During Acceleration
015E	n094	Stall Prevention Level During Running
015F	n095	Frequency Detection Level
0160	n096	Overtorque Detection Function Selection 1
0161	n097	Overtorque/Undertorque Detection Function Selection 2
0162	n098	Overtorque Detection Level
0163	n099	Overtorque Detection Time
0164	n100	Hold Output Frequency Saving Selection
0165	n101	Speed Search Deceleration Time
0166	n102	Speed Search Operation Level
0167	n103	Torque Compensation Gain
0168	n104	Torque Compensation Time Constant
0169	n105	Torque Compensation Iron Loss
016A	n106	Motor Rated Slip
016B	n107	Motor Line-to-neutral Resistance
016C	n108	Motor Leakage Inductance
016D	n109	Torque Compensation Voltage Limiter
016E	n110	Motor No-load Current
016F	n111	Slip Compensation Gain
0170	n112	Slip Compensation Time Constant
0171	n113	Slip Compensation During Regenerative Operation
0172	n114	Number of Transmission Cycle Error Detection (For SI-T/ V7)
0173	n115	Stall Prevention Above Base Speed During Run
0174	n116	Acceleration/deceleration Time during Stall Prevention
0175	n117	Undertorque Detection Function Selection 1
0176	n118	Undertorque Detection Level
0177	n119	Undertorque Detection Time
0178	n120	Frequency Reference 9
0179	n121	Frequency Reference 10
017A	n122	Frequency Reference 11
017B	n123	Frequency Reference 12
017C	n124	Frequency Reference 13
017D	n125	Frequency Reference 14
017E	n126	Frequency Reference 15
017F	n127	Frequency Reference 16
0180	n128	PID Control Selection
0181	n129	PID Feedback Gain
0182	n130	Proportional Gain (P)
0183	n131	Integral Time (I)
0184	n132	Derivative Time (D)
0185	n133	PID Offset Adjustment
0186	n134	Upper Limit of Integral Values
0187	n135	Primary Delay Time Constant for PID Output
0188	n136	Selection of PID Feedback Loss Detection
0189	n137	PID Feedback Loss Detection Level
018A	n138	PID Feedback Loss Detection Time
018B	n139	Energy-saving Control Selection (V/f Control Mode)
018C	n140	Energy-saving Coefficient K2
018D	n141	Energy-saving Control Voltage Lower Limit at 60 Hz
018E	n142	Energy-saving Control Voltage Lower Limit at 6 Hz
018F	n143	Power Average Time
0190	n144	Search Operation Voltage Limit
0191	n145	Search Operation Voltage Step at 100%
0192	n146	Search Operation Voltage Step at 5%
0195	n149	Pulse Train Input Scaling
0196	n150	Pulse Monitor Output Frequency Selection
0197	n151	MEMOBUS Timeover Detection
0198	n152	MEMOBUS Frequency Reference and Frequency Monitor Unit
0199	n153	MEMOBUS Slave Address
019A	n154	MEMOBUS BPS Selection
019B	n155	MEMOBUS Parity Selection
019C	n156	Transmission Waiting Time
019D	n157	RTS Control
019E	n158	Motor Code (Energy-saving Control)
019F	n159	Upper Voltage Limit for Energy-saving Control at 60 Hz
01A0	n160	Upper Voltage Limit for Energy-saving Control at 6 Hz
01A1	n161	Search Operation Power Detection Hold Width
01A2	n162	Time Constant of Power Detection Filter
01A3	n163	PID Output Gain
01A4	n164	PID Feedback Value Selection
01A5	n165	Externally-mounting type braking resistor overheat protection selection
01A6	n166	Input Open-phase Detection Level
01A7	n167	Input Open-phase Detection Time
01A8	n168	Output Open-phase Detection Level
01A9	n169	Output Open-phase Detection Time
01AA	n170	ENTER command operation selection (MEMOBUS communications)
01AB	n171	Frequency reference bias upper limit (UP/DOWN command 2)
01AC	n172	Frequency reference bias lower limit (UP/DOWN command 2)
01AD	n173	DC Injection Braking Proportional Gain
01AE	n174	DC Injection Braking Integral Time Constant
01AF	n175	Reducing Carrier Frequency Selection at Low Speed
01B0	n176	Constant Copy Function Selection
01B1	n177	Constant Read Selection Prohibit
01B2	n178	Fault History
01B3	n179	Software Version No.
[SigDataEnd]

[SigData]-B
0001.0	Run command 1: Run 0: Stop
0001.1	Reverse run 1: Reverse run 0: Forward run
0001.2	External fault 1: Error (EFO)
0001.3	Fault reset 1: Reset command
0001.4	Multi-function input command 1 (Function selected by n050)
0001.5	Multi-function input command 2 (Function selected by n051)
0001.6	Multi-function input command 3 (Function selected by n052)
0001.7	Multi-function input command 4 (Function selected by n053)
0001.8	Multi-function input command 5 (Function selected by n054)
0001.9	Multi-function input command 6 (Function selected by n055)
0001.A	Multi-function input command 7 (Function selected by n056)
0002	Frequency Reference (unit: n152)
0003	V/f gain (1000/100%), Setting range:2.0 to 200.0%
0009.0	Multi-function output reference 1 (1: MA ON　0: MA OFF) (Effective when n057=18)
0009.1	Multi-function output reference 2 (1: P1 ON　0: P1 OFF) (Effective when n058=18)
0009.2	Multi-function output reference 3 (1: P2 ON　0: P2 OFF) (Effective when n059=18)
0020.0	Run command 1: Run 0: Stop
0020.1	Reverse run 1: Reverse run 0: Forward run
0020.2	Inverter operator ready 1: Ready 0: Not ready
0020.3	Fault 1: Fault
0020.4	Data setting error 1: Error
0020.5	Multi-function output 1 (1: MP ON　0: MA OFF)
0020.6	Multi-function output 2 (1: P1 ON　0: P1 OFF)
0020.7	Multi-function output 3 (1: P2 ON　0: P2 OFF)
0021.0	Overcurrent (OC)
0021.1	Overvoltage (OV)
0021.2	Inverter overload (OL2)
0021.3	Inverter overheat (OH)
0021.6	PID feedback loss
0021.7	External Fault (EF, EF0) or Emergency Stop (STP)
0021.8	Hardware Fault (FXX)
0021.9	Motor Overload (OL1)
0021.A	Overtorque Detection (OL3)
0021.B	Undertorque Detection (UL3)
0021.C	Power loss (UV1)
0021.D	Control Power Supply Fault (UV2)
0021.E	Modbus Communications Timeout (CE)
0021.F	Operator Connection Fault (oPR)
0022.0	During Data Write
0022.3	Upper/lower limit fault
0022.4	Consistency fault
0023	Frequency reference (unit: n152)
0024	Output frequency (unit: n152)
0027	Output current (10/1A)
0028	Output voltage reference (1/1V)
0029.2	Input open phase (PF)
0029.3	Output open phase (LF)
002A.0	Operation function stop (STP)
002A.1	Sequence error (SER)
002A.2	Simultaneous FWD/REV run commands (EF)
002A.3	External baseblock (BB)
002A.4	Overtorque detection (OL3)
002A.5	Cooling fan overheat (OH)
002A.6	Main circuit overvoltage (OV)
002A.7	Main circuit undervoltage (UV)
002A.8	Cooling fan fault (FAN)
002A.9	Communications fault (CE)
002A.A	Option card communications error (BUS)
002A.B	Undertorque (UL3)
002A.C	Inverter overheat alert (OH3)
002A.D	PID feedback loss (FBL)
002A.E	Emergency stop (STP)
002A.F	Communications waiting (CAL)
002B.0	Terminal S1 (1: Closed  0: Open)
002B.1	Terminal S2 (1: Closed  0: Open)
002B.2	Terminal S3 (1: Closed  0: Open)
002B.3	Terminal S4 (1: Closed  0: Open)
002B.4	Terminal S5 (1: Closed  0: Open)
002B.5	Terminal S6 (1: Closed  0: Open)
002B.6	Terminal S7 (1: Closed  0: Open)
002C.0	Run 1:Run
002C.1	Zero-speed 1: Zero-speed
002C.2	Frequency agreed 1: Agreed
002C.3	Minor fault (Alarm is indicated)
002C.4	Frequency detection 1 1: Output frequency ≤ (n095)
002C.5	Frequency detection 2 1: Output frequency ≥ (n095)
002C.6	Inverter operation ready 1: Ready
002C.7	Undervoltage detection 1: Undervoltage detection
002C.8	Baseblock 1: Inverter output baseblock
002C.9	Frequency reference mode 1: Other than communications 0: Communications
002C.A	RUN command mode 1: Other than communications 0: Communications
002C.B	Overtorque detection 1: Detection or overtorque fault
002C.C	Undertorque detection 1: Detection or undertorque fault
002C.D	Fault retry
002C.E	Fault (Including MEMOBUS communications timeover) 1: Fault
002C.F	MEMOBUS communications timeover 1: Timeover
002D.0	MA 1: ON 0: OFF
002D.1	P1 1: ON 0: OFF
002D.2	P2 1: ON 0: OFF
002E.0	Frequency Reference loss
0031	Main circuit DC voltage (1/1V)
0032	Torque monitor (1/1 % ; 100 %/Motor rated torque ; with sign)
0037	Output Power (1/1 W: with sign)
0038	PID feedback value (100 % /Input equivalent to max. output frequency ;10/1 % ; without sign)
0039	PID input value (±100 %/±Max. output frequency ; 10/1 % ; with sign)
003A	PID output value (±100 %/±Max. output frequency ; 10/1 % ; with sign)
003D.0	CRC Error
003D.1	Data Length Error
003D.3	Parity Error
003D.4	Overrun Error
003D.5	Framing Error
003D.6	Timeout
0900	ENTER command
0101	n001	Password
0102	n002	Control Mode Selection(Note 6)
0103	n003	RUN Command Selection
0104	n004	Frequency Reference Selection
0105	n005	Stopping Method Selection
0106	n006	Reverse Run Prohibit
0107	n007	Stop Key Selection
0108	n008	Frequency Reference Selection in Local Mode
0109	n009	Frequency Reference Setting Method From Digital Operator
010A	n010	Detecting Fault Contact of Digital Operator
010B	n011	Max. Output Frequency
010C	n012	Max. Voltage
010D	n013	Max. Voltage Output Frequency
010E	n014	Mid. Output Frequency
010F	n015	Mid. Output Frequency Voltage
0110	n016	Min. Output Frequency
0111	n017	Min. Output Frequency Voltage
0112	n018	Selecting Setting Unit for Acceleration/deceleration Time
0113	n019	Acceleration Time 1
0114	n020	Deceleration Time 1
0115	n021	Acceleration Time 2
0116	n022	Deceleration Time 2
0117	n023	S-curve Selection
0118	n024	Frequency Reference 1 (Master Frequency Reference)
0119	n025	Frequency Reference 2
011A	n026	Frequency Reference 3
011B	n027	Frequency Reference 4
011C	n028	Frequency Reference 5
011D	n029	Frequency Reference 6
011E	n030	Frequency Reference 7
011F	n031	Frequency Reference 8
0120	n032	Jog Frequency
0121	n033	Frequency Reference Upper Limit
0122	n034	Frequency Reference Lower Limit
0123	n035	Setting/displaying Unit Selection for Frequency Reference
0124	n036	Motor Rated Current
0125	n037	Electronic Thermal Motor Protection Selection
0126	n038	Electronic Thermal Motor Protection Time Constant Setting
0127	n039	Selecting Cooling Fan Operation
0128	n040	Motor Rotation Direction
0129	n041	Acceleration Time 3
012A	n042	Deceleration Time 3
012B	n043	Acceleration Time 4
012C	n044	Deceleration Time 4
012D	n045	Frequency reference bias step amount (UP/DOWN command 2)
012E	n046	Frequency reference bias accel/decel rate (UP/DOWN command 2)
012F	n047	Frequency reference bias operation mode selection (UP/DOWN command 2)
0130	n048	Frequency reference bias value (UP/DOWN command 2)
0131	n049	Analog frequency reference fluctuation limit level (UP/DOWN command 2)
0132	n050	Multi-function Input Selection 1 (Terminal S1)
0133	n051	Multi-function Input Selection 2 (Terminal S2)
0134	n052	Multi-function Input Selection 3 (Terminal S3)
0135	n053	Multi-function Input Selection 4 (Terminal S4)
0136	n054	Multi-function Input Selection 5 (Terminal S5)
0137	n055	Multi-function Input Selection 6 (Terminal S6)
0138	n056	Multi-function Input Selection 7 (Terminal S7)
0139	n057	Multi-function Output Selection 1
013A	n058	Multi-function Output Selection 2
013B	n059	Multi-function Output Selection 3
013C	n060	Analog Frequency Reference Gain
013D	n061	Analog Frequency Reference Bias
013E	n062	Filter Time Constant for Analog Frequency Reference
013F	n063	Watchdog Error Operation Selection (For SI-T/V7)
0140	n064	Frequency Reference Loss Detection Selection
0141	n065	Monitor Output Type
0142	n066	Monitor Item Selection
0143	n067	Monitor Gain
0144	n068	Analog Frequency Reference Gain (Voltage input from Operator)
0145	n069	Analog Frequency Reference Bias (Voltage input from Operator)
0146	n070	Analog Frequency Reference Filter Time Constant (Voltage input from Operator)
0147	n071	Analog Frequency Reference Gain (Voltage input from Operator)
0148	n072	Analog Frequency Reference Bias (Current input from Operator)
0149	n073	Analog Frequency Reference Filter Time Constant (Current input from Operator)
014A	n074	Pulse Train Frequency Reference Gain
014B	n075	Pulse Train Frequency Reference Bias
014C	n076	Pulse Train Frequency Filter Time Constant
014D	n077	Multi-function Analog Input Function
014E	n078	Multi-function Analog Input Signal Selection
014F	n079	Frequency Reference Bias (FBIAS) Value
0150	n080	Carrier Frequency Selection
0151	n081	Momentary Power Loss Ridethrough Method
0152	n082	Automatic Retry Attempts
0153	n083	Jump Frequency 1
0154	n084	Jump Frequency 2
0155	n085	Jump Frequency 3
0156	n086	Jump Frequency Range
0157	n087	Cumulative operation time function selection
0158	n088	Cumulative operation time
0159	n089	DC Injection Braking Current
015A	n090	DC Injection Braking Time at Stop
015B	n091	DC Injection Braking Time at Startup
015C	n092	Stall Prevention During Deceleration
015D	n093	Stall Prevention Level During Acceleration
015E	n094	Stall Prevention Level During Running
015F	n095	Frequency Detection Level
0160	n096	Overtorque Detection Function Selection 1
0161	n097	Overtorque/Undertorque Detection Function Selection 2
0162	n098	Overtorque Detection Level
0163	n099	Overtorque Detection Time
0164	n100	Hold Output Frequency Saving Selection
0165	n101	Speed Search Deceleration Time
0166	n102	Speed Search Operation Level
0167	n103	Torque Compensation Gain
0168	n104	Torque Compensation Time Constant
0169	n105	Torque Compensation Iron Loss
016A	n106	Motor Rated Slip
016B	n107	Motor Line-to-neutral Resistance
016C	n108	Motor Leakage Inductance
016D	n109	Torque Compensation Voltage Limiter
016E	n110	Motor No-load Current
016F	n111	Slip Compensation Gain
0170	n112	Slip Compensation Time Constant
0171	n113	Slip Compensation During Regenerative Operation
0172	n114	Number of Transmission Cycle Error Detection (For SI-T/ V7)
0173	n115	Stall Prevention Above Base Speed During Run
0174	n116	Acceleration/deceleration Time during Stall Prevention
0175	n117	Undertorque Detection Function Selection 1
0176	n118	Undertorque Detection Level
0177	n119	Undertorque Detection Time
0178	n120	Frequency Reference 9
0179	n121	Frequency Reference 10
017A	n122	Frequency Reference 11
017B	n123	Frequency Reference 12
017C	n124	Frequency Reference 13
017D	n125	Frequency Reference 14
017E	n126	Frequency Reference 15
017F	n127	Frequency Reference 16
0180	n128	PID Control Selection
0181	n129	PID Feedback Gain
0182	n130	Proportional Gain (P)
0183	n131	Integral Time (I)
0184	n132	Derivative Time (D)
0185	n133	PID Offset Adjustment
0186	n134	Upper Limit of Integral Values
0187	n135	Primary Delay Time Constant for PID Output
0188	n136	Selection of PID Feedback Loss Detection
0189	n137	PID Feedback Loss Detection Level
018A	n138	PID Feedback Loss Detection Time
018B	n139	Energy-saving Control Selection (V/f Control Mode)
018C	n140	Energy-saving Coefficient K2
018D	n141	Energy-saving Control Voltage Lower Limit at 60 Hz
018E	n142	Energy-saving Control Voltage Lower Limit at 6 Hz
018F	n143	Power Average Time
0190	n144	Search Operation Voltage Limit
0191	n145	Search Operation Voltage Step at 100%
0192	n146	Search Operation Voltage Step at 5%
0195	n149	Pulse Train Input Scaling
0196	n150	Pulse Monitor Output Frequency Selection
0197	n151	MEMOBUS Timeover Detection
0198	n152	MEMOBUS Frequency Reference and Frequency Monitor Unit
0199	n153	MEMOBUS Slave Address
019A	n154	MEMOBUS BPS Selection
019B	n155	MEMOBUS Parity Selection
019C	n156	Transmission Waiting Time
019D	n157	RTS Control
019E	n158	Motor Code (Energy-saving Control)
019F	n159	Upper Voltage Limit for Energy-saving Control at 60 Hz
01A0	n160	Upper Voltage Limit for Energy-saving Control at 6 Hz
01A1	n161	Search Operation Power Detection Hold Width
01A2	n162	Time Constant of Power Detection Filter
01A3	n163	PID Output Gain
01A4	n164	PID Feedback Value Selection
01A5	n165	Externally-mounting type braking resistor overheat protection selection
01A6	n166	Input Open-phase Detection Level
01A7	n167	Input Open-phase Detection Time
01A8	n168	Output Open-phase Detection Level
01A9	n169	Output Open-phase Detection Time
01AA	n170	ENTER command operation selection (MEMOBUS communications)
01AB	n171	Frequency reference bias upper limit (UP/DOWN command 2)
01AC	n172	Frequency reference bias lower limit (UP/DOWN command 2)
01AD	n173	DC Injection Braking Proportional Gain
01AE	n174	DC Injection Braking Integral Time Constant
01AF	n175	Reducing Carrier Frequency Selection at Low Speed
01B0	n176	Constant Copy Function Selection
01B1	n177	Constant Read Selection Prohibit
01B2	n178	Fault History
01B3	n179	Software Version No.
[SigDataEnd]-B